© 2017 Sensata Technologies
38
Table 3-2, Inverter/Charger Default Settings
04 Battery Type:
This setting identi
fi
es the type of batteries being
used in the system. This provides information to the charger to
determine what voltage level to use to charge the batteries.
05 Charge Rate:
T
his setting can be used to turn off the charger, or
limit the amount of current that the charger can use (leaving more
current available to power loads); or, to ensure small battery banks
are not overheated because of a charge rate that is too high.
06 VAC Dropout:
Sets the minimum AC voltage that must be present
on the AC input before the unit transfers from Standby mode to
Inverter mode. This protects the AC loads from utility outages and
brown-outs.
The ME-RC50 remote also provides the following features:
• allows you to enable an equalize charge for certain battery types
• displays the inverter/charger’s operating status
• displays fault information for troubleshooting
Function
Default Settings
Search Watts
5W
LowBatCutOut
10.0 VDC
Battery AmpHrs
400 AmpHrs
(Absorb Time = 90 minutes)
Battery Type
Flooded - Liquid Lead Acid
(Absorb = 14.6 VDC, Float = 13.4 VDC)
Charge Rate
100%
VAC Dropout
80VAC
Operation