26
13.
Zone 3
Controls R3
14.
Group 1 in each zone
Type 1 CO, Voting mode, Quorum = 1
15.
Group 2 in each zone
Type 2 NO
2
, Voting mode, Quorum = 1
16.
Group 3 in each zone
Type 3 EX, Voting mode, Quorum = 1
17.
Group 4 in each zone
Type 4 NH
3
, Voting mode, Quorum = 1
18.
Group 5 in each zone
Type 5 H
2
S, Voting mode, Quorum = 1
19.
Group 6 in each zone
Type 6 REF, Voting mode, Quorum = 1
20.
Group 7 in each zone
(Currently not used)
21.
Group 8 in each zone
Type 8 O
2
, Voting mode, Quorum = 1
22.
Group 9 in each zone
Type 9 CO
2
Voting mode, Quorum = 1
Description
Carbon
Monoxide
Nitrogen
Dioxide
Combustible
Gas
Ammonia
Hydrogen
Sulfide
Refrigerants
Carbon
Dioxide
Oxygen
Type
CO
NO
2
EX
NH
3
H
2
S
REF
CO
2
O
2
Range
200ppm
20ppm
50% LEL
100ppm
50ppm
1000ppm 5,000ppm
25% v/v
Alarm Level
200ppm
5ppm
20% LEL
75ppm
20ppm
300ppm
4,000ppm 19.5% v/v
Warning
Level
100ppm
3ppm
15% LEL
50ppm
14ppm
200ppm
1,500ppm 20.0% v/v
Rising Level
35ppm
2.5ppm
10% LEL
25ppm
8ppm
100ppm
1,000ppm 20.3% v/v
Falling Level
15ppm
1.2ppm
5% LEL
10ppm
3ppm
50ppm
800ppm
20.6% v/v
Figure 4-22 Default Configuration Settings
4.3.2.4
Change Password
C h a n g e P a s s w o r d
* * * *
Figure 3-23 Change Password
When the first digit is entered to change the password, the panel will prompt for the existing password to be entered (if it hasn’t already
for more detail. Once the current password has been entered, the panel will prompt
for the new password.
4.3.2.5
Configure sensor Type
Sensor Registration
Sensor registration is continuously monitored by the DVP-120. When the currently selected sensor type agrees with the stored registration
information the DVP-120 will remain in normal mode. When new registration information is detected by the DVP-120, for example, if a
different gas type of Macurco sensor was installed, the following message is displayed: “Configuration Changed Any key to save” is
displayed.
Config.
changed
Any Key to save
Figure 4-23.1 Configuration Changed
Pressing any key will prompt the user to enter the password. Once the valid password is entered the new sensor type is saved. The
program does not allow any other activity unless a valid password is entered.
If the DVP-120 is in configuration mode (user is changing the configuration) the registration information is saved in the background and
the message indicating that configuration was changed is delayed until the user goes back to normal mode.