Type: 01 CO
Res.: 1 ppm
Figure 4-23.8 Resolution
“Res.” Defines the resolution used to display the reading, alarm, warning, range, falling level and rising level. It can have values between
1 and 500 when “Dec.” is 0, 50.0 when “Dec.” is 1 and 5.00 when “Dec.” is 2.
Type: 01 CO
Range:
200 ppm
Figure 4-23.9 Sensor Range
“Range” is the value displayed when current measured is 20mA.
Type: 01 CO
Alarm:
200 ppm
Figure 4-23.10 Alarm Level
“Alarm” is the default alarm range.
Type: 01 CO
Warn:
100 ppm
Figure 4-23.11 Warning Level
“Warn” is the default warning range.
Type: 01 CO
Rise:
35 ppm
Figure 4-23.12 Rising Trip Point
“Rise” is the default rising level used in Zone configuration.
Type: 01 CO
Fall:
15 ppm
Figure 4-23.13 Falling Trip Point
“Fall” is the default falling level used in Zone configuration.
For the custom sensor, types default parameters are set to display the current measured above 4 mA. So if the current is 4 mA, it displays
0.00 mA. And when the current is 20 mA it displays 16.00 mA.
4.3.2.6
Enter Password
If the password has not yet been entered, when the first digit of any parameter is entered, the panel will prompt for the current password.
Note that the first digit entered is discarded; it does not count toward the password or toward the parameter entry.