36
Sensors are included or removed from the group by entering the two-digit channel number. After a sensor is added or removed, the list
will be re-sorted so it does not matter in which order the sensors are added or removed. The default is to include all sensors of the
specified type.
When the first digit of a sensor number is entered (a leading zero must be entered if the number is less than ten), the display will prompt
to Add or Remove a sensor from the group.
Z 1 G r o u p 1 N O 2
A d d / R e m o v e : _ 0
Figure 4-46 Add / Remove sensor prompt
When the second digit is entered, the sensor will be added or removed from the control group, provided the sensor is of the proper
type, NO
2
in this example. If the sensor is of the wrong type, or an invalid sensor channel number is entered, the request will not be
completed.
4.3.7.7
Rising Trip Point
Z 1 G r o u p 1 N O 2
R i s i n g : 2 . 5 p p m
Figure 4-47 Rising Trip Point Entry
The default rising trip points are:
Description
Carbon
Monoxide
Nitrogen
Dioxide
Combustible
Gas
Ammonia
Hydrogen
Sulfide
Refrigerants
Carbon
Dioxide
Oxygen
Type
CO
NO
2
EX
NH
3
H
2
S
REF
CO
2
O
2
Rising Level
35ppm
2.5ppm
10% LEL
25ppm
8ppm
100ppm
1,000ppm
20.3% v/v
4.3.7.8
Falling Trip Point
Z 1 G r o u p 1 N O 2
F a l l i n g : 1 . 0 p p m
Figure 4-48 Falling Trip Point Entry
The default falling trip points are:
Description
Carbon
Monoxide
Nitrogen
Dioxide
Combustible
Gas
Ammonia
Hydrogen
Sulfide
Refrigerants
Carbon
Dioxide
Oxygen
Type
CO
NO
2
EX
NH
3
H
2
S
REF
CO
2
O
2
Falling Level
15ppm
1.2ppm
5% LEL
10ppm
3ppm
50ppm
800ppm
20.6% v/v
4.3.7.9
Multiple Sensor Mode
Z 1 G r o u p 1 N O 2
M o d e : 2 V o t i n g
Figure 4-49 Sensor Mode Selection