51
•
Group 2 in each zone Type 2 NO
2
, Voting mode, Quorum = 1
•
Group 3 in each zone Type 3 EX, Voting mode, Quorum = 1
•
Group 4 in each zone Type 4 NH
3
, Voting mode, Quorum = 1
•
Group 5 in each zone Type 5 H
2
S, Voting mode, Quorum = 1
•
Group 6 in each zone Type 6 REF, Voting mode, Quorum = 1
•
Group 7 in each zone (currently unused)
•
Group 8 in each zone Type 8 O
2
, Voting mode, Quorum = 1
•
Group 9 in each zone Type 9 CO
2
, Voting mode, Quorum = 1
Description
Carbon
Monoxide
Nitrogen
Dioxide
Combustible
Gas
Ammonia
Hydrogen
Sulfide
Refrigerants
Carbon
Dioxide
Oxygen
Type
CO
NO
2
EX
NH
3
H
2
S
REF
CO
2
O
2
Range
200ppm
20ppm
50% LEL
100ppm
50ppm
1000ppm 5,000ppm
25% v/v
Alarm Level
200ppm
5ppm
20% LEL
75ppm
20ppm
300ppm
4,000ppm 19.5% v/v
Warning
Level
100ppm
3ppm
15% LEL
50ppm
14ppm
200ppm
1,500ppm 20.0% v/v
Rising Level
35ppm
2.5ppm
10% LEL
25ppm
8ppm
100ppm
1,000ppm 20.3% v/v
Falling Level
15ppm
1.2ppm
5% LEL
10ppm
3ppm
50ppm
800ppm
20.6% v/v
Typical coverage for CO, CO
2
and NO
2
sensors is 5,000 sq. ft. (464.5 sq. m), 900 sq. ft. (83.6 sq. m) for combustibles and other toxic
gases (see the User Instructions for each sensor type for location and coverage details). Extra sensors may be needed near areas where
people work, such as toll booths. Macurco provides only the control panels and sensors. Fans, relays, and other devices are provided by
the contractor. See the appropriate building code for the size of fans and air changes per unit of time.
Figure A-1 System Wiring Diagram