24
•
Configure Sensors
•
Configure Relays, Horn & Strobe
•
Configure Zones
•
Configure Signals
The up and down cursor keys can be used to scroll through the entries in the list, while the left or right key will enter the particular
submenu.
The MENU key will return to normal mode. If any configuration parameters have been changed, the panel will prompt to save the changes.
If the changes are saved, this is the point at which they become effective in controlling the ventilation system and for alarm level detection.
Note that changes to the time and day of week are not considered configuration items; they are saved as soon as they are entered.
NOTE:
For DVP-120B, if baud rate for the panel is changed then “Reading Retries” Modbus parameter must be updated as per the following
table.
Baud Rate
Reading Retries
19200 (Default)
12 (Default)
9600
8
4800
5
Figure 4-16 BACnet baud rate
4.3.2
Configure System Submenu
The system configuration submenu provides entries to:
•
Set the time of day, 24-hour format
•
Set the day of the week, day 1 is Monday
•
Load Default Configuration
•
Change Password
•
Configure Sensor Type
4.3.2.1
Set Time of Day
T i m e : 2 2 : 5 5
D a y : T u e s d a y
Figure 4-17 Set Time of Day
This display example shows that the time is 22:55 (10:55 PM). The underlined characters indicate that the numeric keys can be used to
set the current time of day. When the first digit is entered (and after the password is entered if required), the display will change to show
that the “hour” portion of the time is currently being entered.
T i m e : 0 1 : 5 5
D a y : T u e s d a y
Figure 4-18 Enter Hours
In this example, the first digit entered was 1 (one), and the panel is waiting for the second digit of the hour to be entered. If the second
digit is not entered within five seconds, the time will revert to the previous value. After the second digit of the hour is entered, the display
will prompt for the “minute” entry: