controls and connection ports MODULE
POWER
will be on, if there is a power supply to the module (normal operating status)
TEMP
flash: Warning (there is an over temperature in the unit- over75°C (167°F))
continuous: Output load is disconnected due to over temperature ( - over 90°C ( 194°F))
Fan switch at 40°C (104 °F) at level 1, at 50°C (122°F) at level 2, at 60°C (140°F) at level3.
ERROR
will be on for module failures
LOAD
lights when the threshold is reached according to the connected load:
(All values refer to the use of halogen bulbs)
CTR (Control)
will be on, if a control signal is being received (normal operating status)
Settings on the crates (only necessary for the first start-up)
Addressing Crates:
Set the Crate number using the red switch - make sure to absolutely avoid double numbers !
1 Channel Module 1 x 11,5kVA
2 Channel Module 2 x 5,7kVA
4 Channel Module 4 x 3kVA
with a connected load of:
threshold in%
with a connected load of:
threshold in %
with a connected load of:
threshold in %
5kW
5%
5kW
2%
3kW
2%
4kW
5%
4kW
3%
2kW
3%
3kW
7%
3kW
4%
1kW
5%
2kW
7%
2kW
7%
1kW
10%
1kW
8%
610 W
27%
Minimum rated load for the load function: 540W
Minimum rated load for the load function: 340W
Minimum rated load for the load function: 200W