Environmental conditions:
- access must be controllable, i.e. no access for unauthorised persons.
- Temperature 10 °C - 30 °C (50°F - 86 °F)
- Relative humidity 20 - 90% (no thawing, i.e. the air must not condensate)
- The room air must be dust-free and free of combustible or explosive substances
Air supply
- Cooling and venting the place must be sufficiently dimensioned for the requirements to be met in maximum
continuous operation (for heat built-up, see below).
Heat built-up of the dimmer cabinet under maximum load:
Heat built-up depends on load. Determine the value with:
max load (in kW) x 1,5 / 100 = max heat built-up (in kW)
Technical Data:
Power supply:
230 / 400 V 50 - 60 Hz No manual switching neccessary!
Maximum Load:
Attention: max inductive load is 90% of related power!