Hotline: +49 5251 688865-99
. User's Manual
Network D
immer Processor
61
dim
CHECK LIST:
Mounting
- Substructure sufficiently stable
- Environmental conditions (temperature, air humidity)
- floor space sufficient to open the doors + aisles
- Cabinet sufficiently secured
- Area sufficiently aerated
- Dimmer cabinet sufficiently cooled (stream of cooling air must not be impaired)
- All modules correctly inserted into the Crates and secured
- Swivelling frame secured against opening
Installation
- CAN bus connections made
- terminal resistance in NDP or Crate installed or switched on
- All NDPs connected via network
- Jumper Crate set (1x per Crate)
- Jumper module set (1x per module, max. 3x per Crate)
- NDP software installed
- All lines in and out correctly connected (max. torque observed)
- visual inspection of all cable connections
- Do all module LEDs light up after powering up the cabinet, and is the module detected after scanning?
Configuration
- Passwords assigned
- IP addresses of NDPs set (individually one by one)
- All dimmer patched
- Were all dimmers detected after Scanning and eventually displayed on the grandMA console?
- All channels configured individually one by one