READING
The following parameters can be read out.
ADDRESS
PARAMETER
UNIT
1
Loop 1, Status 1 (See the table below)
---
2
Loop 1, Status 2 (See the table below)
---
3
Loop 1, PV (present value)
Input 1 decimal setting
4
Loop 1, Internal SP (setpoint value)
Input 1 decimal setting
5
Loop 1, Heating MV (control output)
0.01%
6
Loop 1, Cooling MV (control output)
0.01%
7
Loop 1, Local SP (setpoint value)
Input 1 decimal setting
8
Loop 1, Remote SP (setpoint value)
Input 1 decimal setting
9
Loop 2, Status 1 (See the table below)
---
10
Loop 2, Status 2 (See the table below)
---
11
Loop 2, PV (present value)
Input 2 decimal setting
12
Loop 2, Internal SP (setpoint value)
Input 2 decimal setting
13
Loop 2, Heating MV (control output)
0.01%
14
Loop 2, Cooling MV (control output)
0.01%
15
Loop 2, Local SP (setpoint value)
Input 2 decimal setting
67
CT input 1, Current value
0.1A
68
CT input 1, Current value at the control output ON *
1
0.1A
69
CT input 1, Current value at the control output OFF *
1
0.1A
70
CT input 2, Current value
0.1A
71
CT input 2, Current value at the control output ON *
1
0.1A
72
CT input 2, Current value at the control output OFF *
1
0.1A
*1. ‘-1’ (-0.1A) is set when the Controller is unable to measure if the relevant control output does not remain ON or OFF for
the defined time duration in a control cycle. No CT alarm is judged in this case.
Status 1 and Status 2 are assigned with the following status indicators.
BIT
STATUS
PARAMETER
DATA 0
DATA 1
ST
A
TUS 1
LSB
MSB
0
RUN
Loop operating condition
STOP
RUN
1
AUTO
Loop control mode
MANUAL
AUTO
2 RSP
Local / Remote SP selection
Local SP
Remote SP
3 SP_LAMP
SP lamp operation
Not operating
Operating
4 AT
Auto-tuning
Not running
Running
5
POUT_12 *
2
Loop 1 status: Control output 1
Loop 2 status: Control output 2
OFF
ON
6
POUT_34 *
2
Loop 1 status: Control output 3
Loop 2 status: Control output 4
OFF
ON
7 INP_ERR
Input error
Normal
Error
8 INP_R_ERR
Remote SP input error
Normal
Error
9
ALM_HB
Heater wire break alarm
Normal
Alarm
10 ALM_SB
SSR shortcircuit failure alarm
Normal
Alarm
11 ALM_OC
Overload alarm
Normal
Alarm
12 ---
---
---
---
13 ALM_PV1
PV 1 alarm
Normal
Alarm
14 ALM_PV2
PV 2 alarm
Normal
Alarm
15 ALM_PV3
PV 3 alarm
Normal
Alarm
ST
A
TUS 2
LSB
0 EV1
Event input 1
OFF
ON
1 EV2
Event input 2
OFF
ON
2 BANK0
Bank bit 0
OFF
ON
3 BANK1
Bank bit 1
OFF
ON
*2. Control outputs 1 and 3 are read out at Loop 1 status, Control output 2 and 4 are read at Loop 2 status regardless of the
output assignment setting. These bits is always at ‘1’ (ON) with DC output.