LOOP
The Controller has two control loops (loop 1, loop 2) which can be assigned independently with PID and ON/OFF control
operations.
Each loop receives the relevant input to feedback and perform temperature control.
■
OPERATION AT STARTUP
Specify whether the Controller automatically starts operating (RUN) or not (STOP). With STOP setting, it outputs the pre
-
defined ‘MV output at STOP status.’
ADDRESS
PARAMETER
RANGE
DEFAULT
193
Loop 1, Operation at startup
0 : STOP
1 : RUN
0
449
Loop 2, Operation at startup
■
CONTROL MODE AT STARTUP
Specify the control mode at the startup. In MANUAL mode, the control output can be manually manipulated. In AUTO mode,
the Controller starts automatic control operations.
ADDRESS
PARAMETER
RANGE
DEFAULT
194
Loop 1, Control mode at startup
0 : MANUAL
1 : AUTO
0
450
Loop 2, Control mode at startup