CONTROL CYCLE
Specify duty cycle for duty ratio output. Disregarded with DC signal output setting.
ADDRESS
PARAMETER
RANGE
DEFAULT
1282
Control output 1, Control cycle
1.0 to 99.9 seconds
2.0
1442
Control output 2, Control cycle
1602
Control output 3, Control cycle
1762
Control output 4, Control cycle
■
MINIMUM ON/OFF WIDTH
Specify the minimum pulse width for ON and OFF with duty ratio output.
For example, with 1% setting, the output below 1% is output as 0%, while the output above 99% is output as 100%.
ADDRESS
PARAMETER
RANGE
DEFAULT
1283
Control output 1, Minimum ON/OFF width
0.0 to 50.0 %
0.0
1443
Control output 2, Minimum ON/OFF width
1603
Control output 3, Minimum ON/OFF width
1763
Control output 4, Minimum ON/OFF width
■
OUTPUT SCALING 0% / OUTPUT SCALING 100% / OUTPUT 0% / OUTPUT 100%
Specify the internal temperature output range from OUTPUT SCALING 0% to OUTPUT SCALING 100%, and the converted
output range from OUTPUT 0% to OUTPUT 100%.
ADDRESS
PARAMETER
RANGE
DEFAULT
1284
Control output 1, Output scaling 0%
-3200.0 to + 3200.0
(temperature unit)*
4
0.0
1285
Control output 1, Output scaling 100%
100.0
1444
Control output 2, Output scaling 0%
0.0
1445
Control output 2, Output scaling 100%
100.0
1604
Control output 3, Output scaling 0%
0.0
1605
Control output 3, Output scaling 100%
100.0
1764
Control output 4, Output scaling 0%
0.0
1765
Control output 4, Output scaling 100%
100.0
1286
Control output 1, Output 0%
0.0 to 100.0
*5
1287
Control output 1, Output 100%
1446
Control output 2, Output 0%
1447
Control output 2, Output 100%
1606
Control output 3, Output 0%
0.0 to 100.0
0.0
1607
Control output 3, Output 100%
100.0
1766
Control output 4, Output 0%
0.0
1767
Control output 4, Output 100%
100.0
*4. Output scaling 0 to 100 % is valid only when control output is assigned to PV, Internal SP, Local SP or Remote SP. Disre
-
garded if it is assigned to others.
*5. Default value and engineering unit depends upon the model number suffix code as in the table below.
MODEL
OUTPUT 0%
OUTPUT 100%
UNIT
TC10EMPx
0.0
100.0
%
TC10EMAx
4.0
20.0
mA
TC10EMVx
0.0
10.0
V
■
OUTPUT INVERSION
Voltage pulse signal level and open collector output ON/OFF logic can be inverted.
ADDRESS
PARAMETER
RANGE
DEFAULT
1288
Control output 1, Output inversion
0 : Normal
1 : Inverted
0
1448
Control output 2, Output inversion
1608
Control output 3, Output inversion
1768
Control output 4, Output inversion