TC10EM
P. 28 / 43
EM-9581-B Rev.1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
■
MANUAL RESET
Manual reset is used to eliminate errors by offset generated by P control (I = 0, D = 0.0) or PD control (I = 0).
MV (control output) changes from 100% to 0% proportionally to the temperature range set with P value. The MV is converted
so that the MV set with the manual reset value is equal to the SP.
The figure below shows an example of MV value transition against PV when SP is set to 50.0°C, the manual reset value to
40.00%, with P (proportional-only) control (P = 10.0, I = 0, D = 0.0).
[Bank 1]
ADDRESS
PARAMETER
RANGE
DEFAULT
1171
Loop 1, Manual reset
0.00 to 100.00 %
50.00
1811
Loop 2, Manual reset
[Bank 2]
ADDRESS
PARAMETER
RANGE
DEFAULT
1331
Loop 1, Manual reset
0.00 to 100.00 %
50.00
1875
Loop 2, Manual reset
[Bank 3]
ADDRESS
PARAMETER
RANGE
DEFAULT
1491
Loop 1, Manual reset
0.00 to 100.00 %
50.00
1939
Loop 2, Manual reset
[Bank 4]
ADDRESS
PARAMETER
RANGE
DEFAULT
1651
Loop 1, Manual reset
0.00 to 100.00 %
50.00
2003
Loop 2, Manual reset
SP
44°C
54°C
SP=50°C
PV
40%
100%
MV
0%