• ALARM SP TYPE
When the SP is changed, actual target temperature gradually changes in a ramp setting until it reaches the final setpoint.
Choose either the setpoint in the ramp transition or the final setpoint should be used for reference of alarm judgment.
ADDRESS
PARAMETER
RANGE
DEFAULT
326
Loop 1, Alarm 1 SP type
0 : Ramp SP
1 : SP
0
334
Loop 1, Alarm 2 SP type
342
Loop 1, Alarm 3 SP type
582
Loop 2, Alarm 1 SP type
590
Loop 2, Alarm 2 SP type
598
Loop 2, Alarm 3 SP type
• ALARM OUTPUT
Specify the output device for alarms.
When one of the control outputs is specified, be sure also to specify ‘Alarm OR’ or ‘Alarm AND’ with its output assignment.
With ‘Alarm OR’ setting, the output is provided if one or more alarms assigned to it are in true conditions. With ‘Alarm AND’
setting it is provided only if all alarms assigned to it are in true conditions.
ADDRESS
PARAMETER
RANGE
DEFAULT
327
Loop 1, Alarm 1 output
0 : Network only
1 : Control output 1
2 : Control output 2
3 : Control output 3
4 : Control output 4
0
335
Loop 1, Alarm 2 output
343
Loop 1, Alarm 3 output
583
Loop 2, Alarm 1 output
591
Loop 2, Alarm 2 output
599
Loop 2, Alarm 3 output