INSTALLATION
92
+
0.8
−0
92
+
0.8
−0
Pitch ≥122 (4.80)
Pitch ≥147 (5.79)
Mounting bracket: 0.5
–
10 (0.02 to 0.39)
■
PANEL CUTOUT unit: mm (inch)
■
CAUTION
• Degree of protection, IP65 is applicable to the front panel
of the unit with single mounting according to the specified
panel cutout. Not applicable in case of re-mounting. After
installation ensure waterproof of the mounting.
• Install the unit to vertical panel so that its function but
-
tons are at the bottom side. Installing by other direction
will cause degradation of life span or performance due to
rise of the internal temperature.
• Ensure that there is sufficient space for ventilation inside
a panel. Do not install above the devices that generate
high heat such as heaters, transformers or resistors. Ob-
serve at the minimum of 55 mm (2.2”) in vertical direc-
tion, minimum of 30 mm (1.2”) in horizontal direction for
maintenance purpose.
■
HOW TO MOUNT THE UNIT ON A PANEL
1) Remove the mounting brackets.
2) Remove the terminal cover and insert it into the panel
cutout prior to insertion of the unit.
3) Insert the unit into the panel cutout. The watertight pack-
ing must be in place to conform degree of protection, IP65.
Do not remove it.
4) Hang the hooks of the mounting brackets at the square
holes on the upper and bottom side of the unit. Tighten
screws of the brackets until the unit is fixed to the panel.
(torque 0.5 N
.
m)
Panel
Mounting Bracket
Watertight Sealing
■
HOW TO REMOVE THE TERMINAL COVER
Insert the minus tip of a screwdriver into each hole at the
four corners of the cover and pull it to the direction as indi-
cated below to separate the terminal cover.
■
HOW TO REMOVE THE TERMINAL BLOCK
•
The terminal block is separable in two pieces. Loosen two
screws on top and bottom of the terminal block to separate.
•
Be sure to turn off the power supply, input/output signal and
communication signal before separating the terminal block.
• Each terminal block has ID keys so that it can be inserted
to applicable terminal socket only.
Terminal Block Screw
Terminal Block ID Key
Terminal
Block
Separable
Terminal Block ID Key