![background image](http://html1.mh-extra.com/html/m-system/tc10em/tc10em_instruction-manual_3132373037.webp)
TC10EM
P. 37 / 43
EM-9581-B Rev.1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
l
SWITCHING BANKS
Press & hold the [Enter] button in the monitor mode. Choose “BANK” and press [Enter]. Choose the loop which needs to
change bank, then apply among BANK1 to 4. Pressing & holding the [Esc] button or [Enter] button enables to go back to the
monitor mode.
Monitor mode
Press & hold [Esc]
Press & hold [Enter]
Choose BANK
Press & hold [Enter]
All level
Loop1: Choose BANK1 – BANK4
Loop2: Choose BANK1 – BANK4
LOOP1
LOOP2
RUN
BANK
AT
CT
BASIC
ADV
CLR.AL
l
SETTING SP
In the case that SP is displayed in the monitor mode and when the mode is Local SP, pressing [Enter] button enables setting of
SP. Setting of SP updates value of operation while setting is changed. Pressing [Enter] button applies the value and the value
is saved into the non-volatile memory. Pressing [Esc] button cancels the value and it returns to the value before the change.
l
SETTING MV
In the case that MV is displayed in the monitor mode and when the mode is MANUAL, pressing [Enter] button enables setting
of MV. Setting of MV updates value of operation while setting is changed. Pressing [Enter] button apply the value and return
to monitor mode. Pressing [Esc] button cancels the value and it returns to the value before the change.
■
BASIC SETTING MODE
Control type, Universal input and Control output are available in basic setting mode, which is for quick start of operation.
Since PID parameter setting is not included, perform auto tuning after basic setting or set PID parameters in advanced set-
ting. The settings in basic setting mode are included in advanced setting.
l
STARTING BASIC SETTING MODE
Press & hold the [Enter] button in the monitor mode. Choose “BASIC” and press the [Enter]. Pressing the [Enter] at “END”
in the item menu or pressing & holding the [Esc] button in anywhere in the menu enables to return to the monitor mode. In
the case of pressing & holding the [Enter] button, setting items are saved.
l
PARAMETER CHANGE IN BASIC SETTING MODE
Selected item is displayed in the PV Display, setting value is displayed in the SP Display. Choose the item to change and press
the [Enter] button. The first digit of setting value starts blinking and can be changed. For detailed description and setting
range, refer to the page for each setting item.
C.LOGI
I.TYPE
:
:
END
C.TYPE
Press & hold [Enter]
Press & hold [Esc]
Press & hold [Enter]
Choose BASIC
All level
Monitor mode
RUN
BANK
AT
CT
BASIC
ADV
CLR.AL