19
PU-2A USERS
MANUAL EM-9255-C Rev.14
■
100-point LINEARIZER model JFX1
(Group 01)
ITEM
MDFY.
DATA INPUT
DISPLAY
CONTENTS
01
S
MAINTENANCE SWITCH (lock command)
0
MTSW: MON.MODE
MONITOR mode: data monitoring only
1
MTSW: PRG.MODE
PROGRAM mode: “P” marked data modifiable
02
P
Alphabets & No.
TG: XXXXXXXXXX
Tag name entry (10 characters max.)
03
05
P
D
Number (%)
No input
OUTPER XXX.XX
INPPER XXX.XX
Output status monitor (%) & simulation output
Input status monitor (%)
10
D
1
1: LINEARIZER
Multi-point linearizer
11
P
LINEARIZATION
0
LNR NO OPT
Without (proportional output)
1
LNR OPTION
With (Default setting)
19
P
Percentage
FINZER
Fine zero adjustment
Initial status shows actual bias (%). When data is entered, output
(%) is shown.
20
P
Percentage
FINSPN
Fine span adjustment
Initial status shows actual gain (%). When data is entered, output
(%) is shown.
HOW TO PROGRAM SEGMENT DATA FOR LINEARIZATION (JFX1) ....
Non-linear input and their corresponding output values are entered as a percentage of the full range (span). Input
any number of points from 2 to 100 starting from GROUP 02 ITEM 00 in order from the smallest input (X) value. The
operational range is from -15 to +115% of the programmed range.
(Group 02)
ITEM
MDFY.
DATA INPUT
DISPLAY
CONTENTS
00
01
P
P
Percentage
Percentage
X (00): XXX.XX
Y (00): XXX.XX
Input 0 (Linearization point 1)
Output 0 (Linearization point 1)
:
:
:
:
: :
98
99
P
P
Percentage
Percentage
X (49): XXX.XX
Y (49): XXX.XX
Input 49 (Linearization point 50)
Output 49 (Linearization point 50)
(Group 03)
ITEM
MDFY.
DATA INPUT
DISPLAY
CONTENTS
00
01
P
P
Percentage
Percentage
X (50): XXX.XX
Y (50): XXX.XX
Input 50 (Linearization point 51)
Output 50 (Linearization point 51)
:
:
:
:
: :
98
99
P
P
Percentage
Percentage
X (99): XXX.XX
Y (99): XXX.XX
Input 99 (Linearization point 100)
Output 99 (Linearization point 100)