TCH-B100 HAND-HELD PROGRAMMER

PRODUCT PARTS

•   

9 Volt Battery

•    

Remote Programming Cables

STANDARD FEATURES

Compact unit

Easy to use

Provides address setting and reading

Can be used on both sensors and modules

Has the diagnostic ability to display the
analog value

Over 8000 address settings from one battery.

1. Install sensor onto programmer, ensuring that
     sensor protrusions align with programmer grooves.

2. Press the left gray button to switch programmer on.
     A battery check message will appear followed by
     the device's address (Unprogrammed sensors will
     read address 127).

3. Set the required address by incrementing the left
    and right gray buttons (the display will show three
     red flashing dots if the address being programmed
     is different from the device's current address).

4. When the desired address is present, press the red
     button to store that address. The three red dots on
     the display will no longer be present.

ADDRESS SETTING:

SPECIFICATIONS

Rated Voltage:                                         9 VDC

Battery:                                                   9 VDC

Weight:                                                   0.34 lbs

Length:                                                    6 1/4"

Color:                                                      White

APPLICATION

TCH-B100 is designed for use with all analog sensors
and modules.

Continued on back

Summary of Contents for TCH-B100

Page 1: ...uring that sensor protrusions align with programmer grooves 2 Press the left gray button to switch programmer on A battery check message will appear followed by the device s address Unprogrammed sensors will read address 127 3 Set the required address by incrementing the left and right gray buttons the display will show three red flashing dots if the address being programmed is different from the ...

Page 2: ...sensor to factory for servicing DISPLAY MESSAGES bAt On upon power up battery check Also on when battery is low Low battery good for up to 3 000 address setting operation E0 Attempting to set an address beyond 127 E1 Attempting to program an address with no device connected E2 Can not find device after power up E3 Invalid sensor response E4 Can not find the device program E5 Device read error E6 F...

Page 3: ...F CONTAINED SMOKE GENERATOR Specifications subject to change without notice SPECIFICATIONS Rated Voltage 3 VDC Battery 2 D Batteries Combustion Material Punk Stick 7 mm diameter 150 mm long Weight 5 Lbs Length 5 25 to 14 1 feet Color Brown Tests all types of smoke detectors Completely self contained and portable Extends from 5 25 feet to 14 1 feet Internal Smoke Source Non Toxic Smoke Source Unit ...

Page 4: ...amber to the 1 position to turn the power off 2 Compress the telescopic pole to its shortest length 3 Replace the TSE A100 in its carry case 4 Store in a cool dry place 5 For extended storage remove the batteries Testing a Detector continued 1 Rotate the combustion chamber so the 2 arrow line sup with the power indicator screw The fan powers on and a steady flow of smoke is released from the tip o...

Page 5: ...tectors Choose either a Hand held or 15 stainless steel extension pole with easy grip black handle NSTT Tests HochikiAmerica SIJ 24 and SLR 24 835 series smoke detector with a reed switch Choose either a Hand held or 15 stainless steel extension pole with easy grip black handle No combustion material needed No meter batteries or screwdriver required Meets outlined requirements in the NFPA72 Inspec...

Page 6: ...igned to remove the outer covers of the ALG AIE and SLR series sensors detectors NSTT A100 The SIJ 24 and SLR 24 835 series detectors manufactured with magnetically activated dual reed switches for sensitivity testing can be sensitivity tested with the NSTT A100 This meets the requirements of a UL listed calibrated test without the use of combustion materials The NSTT A100 is in compliance with th...

Page 7: ... Type FireNET Family Programming Cable Length 10 feet 3 meters Left Connector 10 Pin Serial Female Right Connector 9 Pin DB9 Female X187 Non Jacketed Version S187 Jacketed Version X187 and S187 are used to program the FireNET family of panels FN P187 Printer Interface cable is used to connect a serial printer to the FireNET family of panels FN V187 VoiceNET Serial Interface Cable is used to interc...

Page 8: ... Length 10 feet 3 meters Left Connector 10 Pin Serial Female Right Connector 25 Pin Serial male SPECIFICATIONS FN V187 CableType VoiceNET Integration Cable Cable Length 10 feet 3 meters Left Connector 10 Pin Serial Female Right Connector 2 Wire Pin male WIRING DIAGRAMS FNV MP INTERFACE REFER TO FIRENET MANUAL V 1 86 OR HIGHER PROGRAMMING INTERFACE PRINTERINTERFACE ...

Reviews: