PU-2A USERS
MANUAL EM-9255-C Rev.14
HOW TO PROGRAM SEGMENT DATA FOR LINEARIZATION ....
Non-linear input and their corresponding output values are entered as a percentage of the full range (span). Input any
number of points from 2 to 16 starting from ITEM 60 in order from the smallest input (X) value. The operational range
is from -15 to +115% of the programmed range.
1) Set 1st point of linearization (input).
2) Press [ITEM] 60 [DATA] [x] ... [ENTER] :
3) Set 1st point of linearization (output).
4) Press [ITEM] 61 [DATA] [x] ... [ENTER] :
5) Repeat the above procedure for all necessary
linearization points.
ITEM
MDFY.
DISPLAY E.G.
CONTENTS
ITEM
MDFY.
DISPLAY E.G.
CONTENTS
60
P
X (01): XXX.XX
Input 1
76
P
X (09): XXX.XX
Input 9
61
P
Y (01): XXX.XX
Output 1
77
P
Y (09): XXX.XX
Output 9
62
P
X (02): XXX.XX
Input 2
78
P
X (10): XXX.XX
Input 10
63
P
Y (02): XXX.XX
Output 2
79
P
Y (10): XXX.XX
Output 10
64
P
X (03): XXX.XX
Input 3
80
P
X (11): XXX.XX
Input 11
65
P
Y (03): XXX.XX
Output 3
81
P
Y (11): XXX.XX
Output 11
66
P
X (04): XXX.XX
Input 4
82
P
X (12): XXX.XX
Input 12
67
P
Y (04): XXX.XX
Output 4
83
P
Y (12): XXX.XX
Output 12
68
P
X (05): XXX.XX
Input 5
84
P
X (13): XXX.XX
Input 13
69
P
Y (05): XXX.XX
Output 5
85
P
Y (13): XXX.XX
Output 13
70
P
X (06): XXX.XX
Input 6
86
P
X (14): XXX.XX
Input 14
71
P
Y (06): XXX.XX
Output 6
87
P
Y (14): XXX.XX
Output 14
72
P
X (07): XXX.XX
Input 7
88
P
X (15): XXX.XX
Input 15
73
P
Y (07): XXX.XX
Output 7
89
P
Y (15): XXX.XX
Output 15
74
P
X (08): XXX.XX
Input 8
90
P
X (16): XXX.XX
Input 16
75
P
Y (08): XXX.XX
Output 8
91
P
Y (16): XXX.XX
Output 16
-15%
0
X01
X02
X03
X04
X05 +115%
Y01
Y02
Y03
Y04
+100% Y05
INPUT
OUTPUT