PU-2A USERS
MANUAL EM-9255-C Rev.14
■
LINEARIZER model xJFX (Group 01)
ITEM
MDFY.
DATA INPUT
DISPLAY
CONTENTS
01
S
MAINTENANCE SWITCH (lock command)
0
MTSW: MON.MODE
MONITOR mode: data monitoring only
1
MTSW: PRG.MODE
PROGRAM mode: “P” marked data modifiable
02
P
Alphabets & No.
TG: XXXXXXXXXX
Tag name entry (10 characters max.)
03
05
06
P
D
D
Number (%)
No input
No input
OUTPER XXX.XX
INPPER XXX.XX
INPVAL XXX.XX
Output status monitor (%) & simulation output
Input status monitor (%) *
1
Input status monitor in actual value, same unit as selected in
ITEM 10.
10
TYPE OF TRANSMITTER INPUT *
2
D
21
Fx-1: 5 – 100mV
D
22
Fx-2: 0.05 – 1V
P
23
Fx-3: 0.5 – 10V
P
24
Fx-6: 1 – 5V
D
25
Fx-A: 4 – 20mA
D
26
Fx-H: 10 – 50mA
11
P
COARSE INPUT RANGE SELECTION
Fx-1
Fx-2
Fx-3
Fx-6/A/H
(± mV)
(± V)
(± V)
0
INPRNG: XXXX
5
0.05
0.5
1
INPRNG: XXXX
10
0.10
1.0
No
2
INPRNG: XXXX
20
0.20
2.0
Adjustment
3
INPRNG: XXXX
50
0.50
5.0
Needed
4
INPRNG: XXXX
100
1.00
10.0
14
15
P
P
Actual value
Actual value
SCLLOW XXXXXX
SCLHIG XXXXXX
Input range scaling 0% value
Input range scaling 100% value
Use the same engineering unit as the coarse range selected in
ITEM 11.
19
P
Percentage
FINZER
Fine zero adjustment
Initial status shows actual bias (%). When data is entered, output
(%) is shown.
20
P
Percentage
FINSPN
Fine span adjustment
Initial status shows actual gain (%). When data is entered, output
(%) is shown.
REMARK 1
: Percentage of the coarse input range selected in ITEM 11.
(Example)
SCALED RANGE
COARSE RANGE
INPUT
DISPLAY
1 – 5 V
0 – 5 V
1 V
20%
0 – 10 V
0 – 10 V
0 V
0%
-5 – +5 V
-5 – +5 V
0 V
0%
-5 – +5 V
-5 – +5 V
-5 V
-100%
REMARK 2
:
Data 23 and 24 are selectable without needing to make hardware change. In order to get 4 – 20 mA or 10 – 50 mA input,
attach a precision resistor to input terminals.