PU-2A USERS
MANUAL EM-9255-C Rev.14
■
THERMOCOUPLE INPUT model xJT (Group 01)
ITEM
MDFY.
DATA INPUT
DISPLAY
CONTENTS
01
S
MAINTENANCE SWITCH (lock command)
0
MTSW: MON.MODE
MONITOR mode: data monitoring only
1
MTSW: PRG.MODE
PROGRAM mode: “P” marked data modifiable
02
P
Alphabets & No.
TG: XXXXXXXXXX
Tag name entry (10 characters max.)
03
04
P
D
Number (%)
No input
OUTPER XXX.XX
OUTTMP XXXX.XX
Output status monitor (%) & simulation output
Output temperature monitor *
1
05
06
07
D
D
D
No input
No input
No input
INPPER XXX.XX
INPVAL XXXXXX
CJMTMP XXX.XX
Input status monitor (%) *
2
Input status monitor in mV
Cold junction compensation temperature (°C)
10
P
TYPE OF THERMOCOUPLE
1
Tc-1:
(PR)
(PR)
2
Tc-2: K
(CA)
K
(CA)
3
Tc-3: E
(CRC)
E
(CRC)
4
Tc-4: J
(IC)
J
(IC)
5
Tc-5: T
(CC)
T
(CC)
6
Tc-6: B
(RH)
B
(RH)
7
Tc-7: R
R
8
Tc-8: S
S
9
Tc-9: WRe 5-26
WRe 5-26
0
Tc-0: N
N
14
15
P
P
Actual value
Actual value
SCLLOW XXXXXX
SCLHIG XXXXXX
Input range scaling 0% value
Input range scaling 100% value
Use the same temp. unit as selected in ITEM 21.
19
P
Percentage
FINZER
Fine zero adjustment
Initial status shows actual bias (%). When data is entered, output
(%) is shown.
20
P
Percentage
FINSPN
Fine span adjustment
Initial status shows actual gain (%). When data is entered, output
(%) is shown.
21
P
TEMPERATURE SCALE
0
1
2
TMPSCL: [°C]
TMPSCL: [°F]
TMPSCL: [K]
Program ITEM 21 first before ITEM 14/15 when °F or K calibra
-
tion is needed. This procedure is necessary whenever thermocou-
ple type is changed.
REMARK 1
:
Temperature is indicated in the unit selected in ITEM 21.
REMARK 2
: Percentage of the input range without zero scaling (0 to upper-range value).
(Example)
SCALED RANGE
COARSE RANGE
INPUT
DISPLAY
100 – 1000°C
0 – 1000°C
200°C
20%