PU-2A USERS
MANUAL EM-9255-C Rev.14
■
3-wire RTD INPUT model xJR (Group 01)
ITEM
MDFY.
DATA INPUT
DISPLAY
CONTENTS
01
S
MAINTENANCE SWITCH (lock command)
0
MTSW: MON.MODE
MONITOR mode: data monitoring only
1
MTSW: PRG.MODE
PROGRAM mode: “P” marked data modifiable
02
P
Alphabets & No.
TG: XXXXXXXXXX
Tag name entry (10 characters max.)
03
04
P
D
Number (%)
No input
OUTPER XXX.XX
OUTTMP XXXXXX
Output status monitor (%) & simulation output
Output temperature monitor *
1
06
D
No input
INPVAL XXXXXX
Input status monitor in Ω.
10
TYPE OF RTD
P
P
31
32
RB-1: Pt 100
RB-2: JPt 100
Pt 100 (JIS ’89)
JPt 100 (JIS ’89)
D
D
33
34
RB-3: Pt 50
RB-4: Ni 508.4
Pt 50 Ω (JIS ’81)
Ni 508.4 Ω
P
36
RB-6: Pt 100_97
Pt 100 (JIS ’97, IEC)
14
15
P
P
Actual value
Actual value
SCLLOW XXXXXX
SCLHIG XXXXXX
Input range scaling 0% value
Input range scaling 100% value
Use the same temp. unit as selected in ITEM 21.
19
P
Percentage
FINZER
Fine zero adjustment
Initial status shows actual bias (%). When data is entered, output
(%) is shown.
20
P
Percentage
FINSPN
Fine span adjustment
Initial status shows actual gain (%). When data is entered, output
(%) is shown.
21
P
TEMPERATURE SCALE
0
1
2
TMPSCL: [°C]
TMPSCL: [°F]
TMPSCL: [K]
Program ITEM 21 first before ITEM 14/15 when °F or K calibra
-
tion is needed. This procedure is necessary whenever RTD type is
changed.
REMARK 1
: Temperature is indicated in the unit selected in ITEM 21.
REMARK 2
: Percentage of the input range without zero scaling (0 to upper-range value). See model xJT.
■
POTENTIOMETER INPUT model xJM (Group 01)
4-wire RTD INPUT model 10JRE (Group 01)
ITEM
MDFY.
DATA INPUT
DISPLAY
CONTENTS
01
S
MAINTENANCE SWITCH (lock command)
0
MTSW: MON.MODE
MONITOR mode: data monitoring only
1
MTSW: PRG.MODE
PROGRAM mode: “P” marked data modifiable
02
P
Alphabets & No.
TG: XXXXXXXXXX
Tag name entry (10 characters max.)
03
05
P
D
Number (%)
No input
OUTPER XXX.XX
INPPER XXX.XX
Output status monitor (%) & simulation output
Input status monitor (%) *
1
10
P
LINEARIZATION
41
Pm-1: straight
Without
42
Pm-2: curved
With (ITEM 60 to 91 for data input) *
2
19
P
Percentage
FINZER
Fine zero adjustment
Initial status shows actual bias (%). When data is entered, output
(%) is shown.
20
P
Percentage
FINSPN
Fine span adjustment
Initial status shows actual gain (%). When data is entered, output
(%) is shown.
REMARK 1
: Percentage of the total resistance
REMARK 2
: See LINEARIZER model xJFX table for detailed explanation on curve data programming (ITEM 60 to 91). You
can also specify output percentage for unused resistance range by the linearization table.