PU-2A USERS
MANUAL EM-9255-C Rev.14
ITEM
MDFY. DATA INPUT
DISPLAY
CONTENTS
23
P
running ave qty
Specifying number of samples used for calculating transfer (run
-
ning) average
JPAD
JRPD
JPRD
JPSM
JFRD
DATA, ENTR
Indicating current setting
DATA, 1, ENTR
DATA, data, ENTR
running ave off
X data
Transfer average function cancelled
Entering number of samples, data : 2 – 8
DATA, UP
DATA, DOWN
Display data increases.
Display data decreases.
24
P
alarm threshold
Specifying alarm setpoint
JPAD
JPQD
JRPD
JRQD
JARP
JAPD
DATA, ENTR
Indicating current set value (%)
DATA, data, ENTR XXX.XX%
Entering setpoint (0 – 100.00%)
data : 0 – 100.00
DATA, UP
DATA, DOWN
Display data increases.
Display data decreases.
25
P
alarm hysteresis
Specifying hysteresis (deadband) for alarm setpoint
JPAD
JPQD
JRPD
JRQD
JARP
JAPD
DATA, ENTR
Indicating current set value (%)
DATA, data, ENTR XXX.XX %
Entering setpoint (0 – 20.00%)
data : 0 – 20.00
DATA, UP
DATA, DOWN
Display data increases.
Display data decreases.
26
P
alarm mode
Specifying alarm operation mode
JPAD
JPQD
JRPD
JRQD
JARP
JAPD
DATA, ENTR
Indicating current mode
DATA, 0, ENTR
DATA, 1, ENTR
Low alarm trip
High alarm trip
27
P
overflow mode
Specifying output mode at counter overflow
JPQD
DATA, ENTR
Indicating current mode
DATA, 0, ENTR
DATA, 1, ENTR
overflow : reset
overflow : halt
Counter is reset to 0% and restart counting.
Counter is stopped at the span count value.
For returning to 0%, external reset input is needed.
28
P
initial count sw
Specifying output mode at power ON
JPQD
JRQD
DATA, ENTR
Indicating current mode
DATA, 0, ENTR
DATA, 1, ENTR
DATA, –, ENTR
count : cold start
count : hot start
count (mem) reset
Counter starts from 0%.
Counter starts from the value stored at power OFF.
Counter value stored in non-volatile memory is deleted.
29
P
encdr prescaler
Prescaling the rotary encoder signal
JRPD
JRQD
DATA, ENTR
Indicating current scale
DATA, 0, ENTR
DATA, 1, ENTR
DATA, 2, ENTR
DATA, 3, ENTR
DATA, 4, ENTR
prescaler : 1/4
prescaler : 1/2
prescaler : 1/1
prescaler : 2/1
prescaler : 4/1
Scaling input pulse by 1/4 before measuring
Scaling input pulse by 1/2 before measuring
Measuring without scaling
Scaling input pulse by 2/1 before measuring
Scaling input pulse by 4/1 before measuring
DATA, UP
DATA, DOWN
Display data No. increases.
Display data No. decreases.
30
P
DATA, ENTR
measuring freq
Manual frequency measuring
Indicating current status
(JPAD JRPD)
JARP
JAPD
meas completed
meas in progress
Measuring completed or not started yet
Measuring not completed yet
DATA, 0, ENTR
meas quitted
Manual frequency measuring stop command
Indicating that manual measuring is stopped.
DATA, 1, ENTR
meas started
Manual frequency measuring start command
Indicating that manual measuring is started.
This ITEM can be used in PROGRAM mode only (not in a measuring cycle).
31
P
fiz capturing
Capturing lower range input frequency
(JPAD JRPD)
JARP
JAPD
DATA, ENTER
Current set value
DATA, 1, ENTR
fiz captured
Frequency captured