54
47DM OPERATING MANUAL EM-9510-B Rev.6
3
Press Alarm/
↓
or Scale/
↑
button to go to the input scaling
value Span setting.
• The input scaling value Span is indicated.
• The SD indicates ‘SPAN’.
• ‘Spn’ and ‘Tch’ indicators turn on.
4
Press Up button to go to the teach calibration (Span) setting.
• ‘Tch’ indicator starts blinking in red.
5
Apply 100% input and press Up button to register the value.
• The teach calibration (Span) is registered.
• ‘Tch’ indicator turns on in green.
IMPORTANT
• Confirm that the input signal is stable before pressing Up button.
• Set ‘input scaling value Zero + 10% of total resistance ≤ input scaling value Span’.
6
■
TO GO ON TO SET THE DISPLAY SCALING VALUE SPAN,
Skip to Step 3 in “3.4 STEP 4. DISPLAY SCALING VALUE SPAN”.
■
TO QUIT,
Hold down Alarm/
↓
or Scale/
↑
button for 1 second or more to return to Measuring Mode.
NOTE
■
IF THE FRONT BUTTONS ARE LEFT UNTOUCHED…
• The display goes back automatically to Measuring Mode after the specified time period (default: 15 sec.).
• This time period (automatic return time) is configurable. (Refer to 14. GOING BACK AUTOMATICALLY TO MEASUR-
■
TO ABORT A SETTING…
• Hold down Max/Min button for 1 second or more in Step 4 to return to Measuring Mode without applying the last
changes.
• If you get lost in a setting mode, you can execute initialization. (Refer to 34.2 INITIALIZING SETTING VALUES.)