56
47DM OPERATING MANUAL EM-9510-B Rev.6
3
Press Alarm/
↓
or Scale/
↑
button to go to the display scaling
value Span setting.
• The display scaling value Span is indicated.
• The SD indicates ‘DISP-S’.
• ‘Spn’ indicator turns on.
NOTE
Skip to Step 7 if the default value is acceptable.
4
Press Shift button to shift the display into the setting standby
mode.
• The sixth digit starts blinking, to which you can apply changes.
5
Press Shift and Up buttons to set to ‘1000.00’.
• Press Shift button to go to the next digit and Up button to change
the blinking value.
NOTE
• ‘1000.00’ is a display example. Set any value within the range of -20000 to 100000.
• The decimal point position depends on the decimal point position setting. Disregard the decimal point here.
• The negative sign (-) must be set to the 6th digit. For example, set ‘-004.00’ instead of ‘-4.00’.
6
Press Alarm/
↓
or Scale/
↑
button to apply the new setting.
• And the next parameter setting is indicated.
NOTE
• Press Alarm/
↓
button, and the decimal point position will be indicated (‘D-POINT’ on the SD).
• Press Scale/
↑
button, and the input scaling value Span will be indicated (‘SPAN’ on the SD).
Blinking
Blinking