35.4.2 SCALING SETTING MODE
NOTE
The bargraph lower and upper limits are disabled with “no bargraph” selected for the bargraph type parameter.
Analog output type
4-20MA, 0-5V, 5V,
10V, 0-20MA
Analog output
function mode
DISPLY, SCALE
Analog output 0%
-20000 to 100000
Analog output 100%
-20000 to 100000
Analog output 0%
adjustment
UP (increasing),
DOWN (decreasing)
Analog output 100%
adjustment
UP (increasing),
DOWN (decreasing)
Bargraph lower limit
-20000 to 100000
Bargraph type
INC (unidirectional bar)
INCR (unidirectional bar (reverse LCD))
DEV (bidirectional bar)
DEVR (bidirectional bar (reverse LCD))
OFF (no bargraph)
Display scaling value Span
-20000 to 100000
Input scaling value Span
Display scaling value Zero
-20000 to 100000
Input scaling value Zero
for ≥ 3 sec.
for ≥ 1 sec.
or
Measurement
started
Measurement
stopped
Scaling Setting Mode
Measuring Mode
Teach calibration
(Zero)
Teach calibration
(Span)
Bargraph upper limit
-20000 to 100000
Selectable only with the DC output code ‘1’.
*
No decimal point, 10
-1
to 10
-4
Decimal point position