47DM OPERATING MANUAL EM-9510-B Rev.6
3.2 STEP 2. DISPLAY SCALING VALUE ZERO
3.2.1 OPERATING PROCEDURE
NOTE
The left figure shows a display example (default display
scaling value Zero). The display depends on the set-
tings.
1
Confirm the wiring, and turn on the power.
• All the indications turn on for approximately 3 seconds and then
the display moves on to Measuring Mode.
NOTE
• Indication ‘S.ERR’ may blink, which shows the input out of the meas-
uring range and does not show the unit failure.
• The SD indicates the bank No. with the bank switching set to “ena-
bled”.
2
Hold down Scale/
↑
button for 3 seconds or more to move on to
Scaling Setting Mode.
• The input scaling value Zero is indicated.
• The SD indicates ‘ZERO’.
• ‘Zro’ and ‘Tch’ indicators turn on.
NOTE
Some alarm indicators turn on with the parameter display. The alarm indication is due to the last status before mode
transition held but does not show the unit failure.
3,6
2,3,
6
4,5
5
■
Immediately after power on (all indicators on)
■
Measuring Mode
*
1 Display depends on the settings and input.