CP-600DC-ID Guide

 

84744 Rev 2 Sept 2015 

GENERAL 

The CP-600DC-ID is a split core CT meant for 
operation with the Megger Power Quality Line 
of Instruments. This current clamp will measure 
both AC and DC current. 

This CT is NOT 

powered by the unit.

 This CT requires a 9V 

battery to operate. 

NOTE:

 

  

If using this CT with a PA-9 series 

power quality analyzer the PA-9 
current full scale value MUST be 
set to 1000.

 

SAFETY and SYMBOLS 

 

WEEE 

The crossed out wheeled bin placed 
on Megger products is a reminder 
not to dispose of the product at the 
end of its life with general waste.

 

Megger

 

is registered in the UK as a 

Producer of Electrical and 
Electronic Equipment. The 
Registration No is WEE/DJ2235XR. 

 

Equipment complies with current 
EU directives.

 

 

Application around or removal from 
hazardous live conductors is 
permitted. 

 

Equipment protected throughout by 
double insulation. 

CAUTION

 

is defined as a condition 

or practice which could result in 
damage to or destruction of the 
equipment or apparatus under test. 

WARNING is defined as a condition 
or practice which could result in 
personal injury or loss of life. 

Safety warnings are precautions that must be 
read and understood before the instrument is 
used. They must be observed during use. 

Do not leave the instrument connected to the 
system under test when not in use. 

Always use extreme caution when connecting 
the instrument around bare conductors, under 
fault conditions, high voltage or currents may 
be present and may pose a shock hazard. 

Personal protective equipment (PPE) must be 
used during the installation and removal of this 
instrument from hazardous live connectors. 

Do not touch circuit connections or any metal 
that is exposed due to damaged insulation. 

Do not use the instrument or connect it to any 
external system if it shows any visible signs of 
damage, malfunction or if it has been stored in 
unfavorable conditions. 

Always inspect the instrument prior to use.  

Replace any defective parts or return the 
instrument to an authorized center for repair. 

Do not use the instrument or connect it to any 
external system if the enclosure is open or any 
parts of the enclosure are missing. 

Only use specified batteries as described by 
this document, if applicable. 

The instrument shall not be used if any parts 
are damaged. 

Always connect the probe to the instrument 
prior to connecting to the source. 

This instrument is not intrinsically safe and 
must not be used in hazardous atmospheres. 

If this equipment is used in the manner not 
specified by the manufacturer, the protection 
provided by the equipment may be impaired.

SPECIFICATIONS 

Working / Common Mode Voltage: 600Vrms 

Current Range 

1 to 600A 

Scale 

1mV / Amp 

Load Impedance 

>100K

 / 100pF 

Bandwidth: 

DC to10KHz @ -3dB 

Accuracy:    
400A Range  

1 to 100A = 1.5% of reading 
+/- 1A 
100 to 400A = 2% reading 

Accuracy    
600Adc Range 

400 to 600A (DC ONLY) = 
2.5% of reading 

Phase Shift  

1 to 200A 

 2.5

°

 

200 to 400A 

 2.0

°

 

Overload  

2000Adc & 1000Aac 
Continuous up to 1KHz 

Power Source 

9V Alkaline Batteries NEDA 
1604A, IEC 6LR61 (120-HR 
LIFE) 

Jaw Opening 

1.2 inches (31mm) 

Dimensions 

8.8x3.82x1.73” 
(224x97x44mm) 

Weight  

15oz (440g) 

Operating 
Temperature 

-10 – 55C 

Storage 
Temperature 

 -40 – 80C 

Humidity  

10-35C 90% +/- 5% NC 
40-55C 70% +/- 5% NC 

IEC61010-2-032: 2012 
EN50081-1 Class B 
EN50082-2 Electrostatic Discharge; IEC61000-4-2 
Radiated Field IEC61000-4-3 
Fast Transient IEC61000-4-4 
Magnetic Field 50/60Hz IEC61000-4-8 
600V CAT III, Pollution Category 2 

*Reference conditions: 23°C ±3°K, 20 to 75% RH, 48 to 
65 Hz, external magnetic field < 40 A/m, no DC 
component, no external current carrying conductor, test 
sample centered. Load impedance 1M