Appendix IV
____________________________________________________________________________________________
68 | Installation, Operation & Maintenance Instructions EASYCHLORGEN
Notes:
Notes for CI valves software version 332.2
Starting a manual Regeneration
Press and hold the REGEN button until the motor starts.
Set a delayed regeneration
Press the REGEN button (REGEN TODAY) will flash on screen) press
the REGEN button again to clear.
Advancing through a regeneration
Press the REGEN button to move to the next stage of regeneration.
Doing a soft reset
Press & Hold REGEB & NEXT for 3 seconds. (resets valve in error).
Doing a total reset
Press & Hold REGEB & NEXT for 3 seconds, then press & hold the
UP & DOWN buttons together for 3 seconds. (resets valves history).
Changing the service display
Press NEXT to toggle to the next available display.
Note
Options
1
Off
Feature not used (standard setting)
ALT A
Set on primary valve is using a standard duplex alternating system (Duplex only)
ALT B
Secondary valve if using a standard duplex alternating system (Duplex only)
SYS
If being used with a system controller.
SEPS
Used if a separate source MAV is being fitted (requires 3 way Mav valve)
nHbP
Used if a No Untreated Water valve is being fitted (no untreated water during regen)
2
Off
Feature not used (standard setting) If used the following options are available)
dpon0
If the contact is closed it will initiate an immediate regeneration.
dPdEL
If the contact is closed it will initiate a delayed regeneration.
Hold
If the contact is closed a regeneration will be prevented.
3
Auto
Capacity is automatically calculated and a reserve will be estimated.
OFF
Regenerations will be controlled from the day override setting (user settings)
M³
Regeneration will occur immediately when the set capacity has expired.
If off or M³ is selected the hardness setting will not display in settings.
4
NORMAL
Regenerations will occur at the pre set time. (not available on alternating duplex)
On 0
Regenerations will occur immediately when capacity reaches zero.
Normal on 0 Regeneration will occur at the preset time when volume is below the reserve or if
volume is below the reserve after 10 minutes of no water usage.
5
OFF
Feature not used.
Time on
Activates after a set time from the start of a regeneration for a set period of time.
L Softening on Activates in service after a set number of litres for a set time and deactivates after
a set period of flow stops.
L Softening Regen on
As above but during regeneration.
6
OFF
Feature not used.
Time on
Activates after a set time from the start of a regeneration for a set period of time.
L Softening on Activates in service after a set number of litres for a set time and deactivates after
a set period of flow stops.
L Softening Regen on
As above but during regeneration.
Error
Activates whenever the valve enters an error mode.
7
Add the KG of salt added to the brine bin each fill, does not show for 1.5 & 2" valves.
8
OFF
Standard setting.
Delay
The last two cycles can be delayed (Rinse & Fill) this delays until the on line unit is
depleted to 10%.
8a
PrE
A pre rinse can be set to rinse the next cylinder before going into service (1" 2" & 1" TT)
9
PrE
A pre rinse can be set if required of up to 20 minute duration.