P30P-09A 84 User's manual
1A, 230V
0 ... 230..360
5A, 230V
0 ... 1150..1800
Active power factor
pf
-1 .. 0 .. 1
0.5 %
Tangent
φ
-1.2 .. 0 .. 1.2
1 %
Angle between U, I
-180
o
...180
o
1 %
(for
<-5
o
...5
o,
,
I > 10% I
N
, U >10%U
N
)
Active energy (+/-),
apparent
0 .. 9 999 999.9 kWh
0.5 %
Reactive energy
0 .. 9 999 999.9 kvarh
1
.0 %
THD
0...100%
5 %
K
U
-
voltage ratio,
K
I
–
current ratio
During semi-indirect and indirect measurements of I, U, P, Q and S, maximum range of values displayed
on the LCD is -99999G...99999G. Ranges depend on the transformer input and output parameters (
U
prim., U sec, I prim., I sec
).
●
minimum voltage measurement synchronization 12.5V (version 230V), 6V (version 100V)
●
minimum current measurement synchronization 100 mA
Outputs:
Main analog output OUT1
●
analog, programmable, galvanically isolated
* current I
OUT
= 0/4...20 mA, load resistance ≤ 500 Ω; or
* voltage U
OUT
0...10 V, load resistance ≥ 500 Ω,
●
analog output class
0.1;
●
processing time
< 200 ms
●
overload
1.2 I
OUT,
or 1.2
U
OUT,
Additional analog output (OUT2, interchangeably with relay output)
●
1 analog output (interchangeably with alarm output)
* current I
OUT
= 0/4...20 mA, load resistance ≤ 250 Ω; or
* voltage U
OUT
0...10 V, load resistance ≥ 500 Ω,
●
class
0.5
●
processing time
< 500 ms
●
overload
1.1 I
OUT
, or 1.1 U
OUT
,