P30P-09A 31 User's manual
7606
AnIn Lo1
-200
-200.0
7607
AnIn Hi1
1200
1200.0
7608
AnOutLo1
4000
*
4000
*
7609
AnOutHi1
20000
*
20000
*
4102
OvOutLo1
0
0
4103
OvOutHi1
1000
1000
4104
OvrOutL1
1500
*
1500
*
4105
OvrOutH1
3500
*
3500
*
•
value in the register is an integer value multiplied by 1000 (4mA → value 4000)
•
Fig. 11 Analog output with threshold limit handling on
Example: Main analog output (no. 1) configuration for the time reaction
Individual characteristics of the analog output no. 1 (current) are set so that the output reacts
to the real time (hour*100+minute), i.e. for the 00:00 hours, the expected value is 4 mA and for 23:59
hours, the expected value is equal to 20 mA:
Table 13
Register no.
Parameter symbol
in the menu
Register
value
Parameter value symbol in the
menu
4100
ParamAn1
16
time
4101
OverSer1
0
off
7606
AnIn Lo1
0
0.0
7607
AnIn Hi1
23.59
23.59
7608
AnOutLo1
4
4
7609
AnOutHi1
20
20.0