P30P-09A 58 User's manual
4024
Disp.Reg
w/r
0....65535
7509 Number of the register displayed on the lower
display line (to display float type register value
within the 16-bit registers input corresponding
number of the 32-bit register)
4025
w/r
0...1
0
Resetting of the alarm signal support on LED (A1,
A2)
4026
Param.A1
w/r
0...16
0
Input value controlling the alarm 1
Value
Description
0
Register values 7500 - voltage
1
Register values 7501 – current
2
Register values 7502 – active power
3
Register values 7503 – reactive power
14
Register values 7514 - temperature
15
Second value displayed
16
Clock
4027
Type A1
0
Alarm 1 type (description – Fig. 12)
Value
Description
0
n-on
1
n-off
2
on
3
off
4
h_on
5
h_off
4028
DlyOnA1
w/r
0...900
0
Alarm 1 activation delay time (s)
4029
DlyOffA1
w/r
0...900
0
Alarm 1 deactivation delay time (s)
4030
OnLockA1
w/r
0...900
0
Alarm 1 re-activation delay time (s)
4031
SgKeepA1
w/r
0...1
1
Alarm 1 signalization latch (LED flashing)
Value
Description
0
Latch disabled
1
Latch enabled
4032
w/r
RESERVED
4033
Param.A2
w/r
0...14
0
Input value controlling the alarm 2
Value
Description
0
Register values 7500 - voltage
1
Register values 7501 – current
2
Register values 7502 – active power
3
Register values 7503 – reactive power
..
..
14
Register values 7514 - temperature