P30P-09A 59 User's manual
15
Second value displayed
16
Clock
4034
Type A2
0
Alarm 2 type (description – Fig. 12)
Value
Description
0
n-on
1
n-off
2
on
3
off
4
h_on
5
h_off
4035
DlyOnA2
w/r
0...900
0
Alarm 2 activation delay time (s)
4036
DlyOffA2
w/r
0...900
0
Alarm 2 deactivation delay time (s)
4037
OnLockA2
w/r
0...900
0
Alarm 2 re-activation delay time (s)
4038
SgKeepA2
w/r
0...1
1
Alarm 2 signalization latch (LED flashing)
Value
Description
0
Latch disabled
1
Latch enabled
4039...4
041
w/r
RESERVED
4042
Mode
w/r
0...2
0
Interface RS-485 operating mode
0
The transducer serves as Slave on the RS485
line, waiting for the queries and responds if
they are addressed
1
The transducer monitors the traffic on the
RS485 line and reacts to data exchange
between the external devices working as
Master and Slave
2
Transducer uses Master function on the RS-
485 link, sends queries and analyzes
responses received from the Slave device
4043
Address
w/r
0...247
1
Transducer address for RS-485 interface. Entering
the value "0" disables the function.
4044
ModeUnit
w/r
0...3
0
Interface RS-485 transmission mode
0
RTU 8N2
1
RTU 8E1
2
RTU 8O1
3
RTU 8N1
4045
BaudRate
w/r
0...7
1
RS-485 interface baud rate
Value
Description
0
4800 bit/s
1
9600 bit/s
2
19200 bit/s
3
38400 bit/s
4
57600 bit/s