P30P-09A 41 User's manual
After starting the eCon software, go to the
Communication
tab and set baud rate, mode,
transducer address and RS-485 interface port. Then click the
Connect
icon and read all set parameters
(it is necessary to revert them later). Next, click the
Firmware update
link, the LUMEL UPDATER (LU)
software will appear – Fig. 24. Press the
Connect
button.
The
Messages
information window displays
information concerning upgrade process. If the port is opened correctly, a
Port opened
message
appears. Upgrade mode is enabled using either of the two methods: remotely via LU (using eCon
settings: address, mode, baud rate, COM port) and by turning a transducer on while pressing the
following button:
- update with standard communication parameters, i.e.: baud rate: 9600 kb/s,
mode: 8N2 or with the following button pressed:
- update with recommended communication
parameters, i.e.: baud rate: 115200 kb/s, mode: 8N2. When all LEDs are lit and the „
Connect
UPDATER
”
message is displayed in the upper display line, the transducer is ready for the
communication with PC. When transducer successfully connects to the LUMEL UPDATER software, LU
program displays the following message:
Device found: P30P
, main program version and connected
device bootloader version, while the transducer display shows the ”
Device is ready
”
message.
Next, press the following button:
...
” to load the file with new software version in LUMEL UPDATER
software. If the file is opened correctly, a
File opened
message is displayed in LU program window.
Press the
Send
button. During update, signal LEDs are being lit in sequence, and the lower display line
shows the percentage progress of the update. When upgrade is successfully completed, the transducer
starts normal operation while the information window displays
Done
message and upgrade elapsed
time.
Current software version can be checked by reading the welcome message when switching the
transducer on.
Note:
Software update is possible only when transducer is connected to PC (no other
Master
devices present on RS-485).
Caution:
Turning the transducer power supply off during upgrade process may result in
permanent damage!
5.8. Measuring values archiving
5.8.1 Transducer memory structure
P30 transducers are by default (regardless of the version) are equipped with 4MB internal
memory to store data registered by the transducer. Any displayed value (registers 7500...7515) can be a
registered parameter with an exception of meter values (energy meters). Second displayed value can be
registered optionally.
Internal memory of the transducer can store up to 534336 records. Memory is
organized as a circular buffer. After the memory is full, the oldest data are overwritten first. Internal
archive can be read, copied and deleted.