P30P-09A 56 User's manual
ent type
Value
0
1-phase network parameters
1
3-phase network parameters
4002
DemandTm
w/r
0...3
Method of averaging of the P, S and I.
Value
0
15-minute moving window, value not
synchronized with the clock
1
15-minute moving window, value
synchronized with the clock
2
30-minute moving window, value
synchronized with the clock
3
60-minute moving window, value
synchronized with the clock
4003
Averag.
Averaging time of the instantaneous values U, I, P,
Q, S, PF, tg, f,
0
No averaging, value based on 8
intervals
1
200ms
2
500ms
3
1s
4
3s
5
5s
6
10s
4004
Synchro
w/r
0...1
0
Measuring input synchronization
Value
0
Voltage
1
Current
4005
I direct
w/r
0...1
0
Current direction
Value
0
Normal
1
Reversed
4006..
4007
RESERVED
4008
Clear En
w/r
0...5
0...5
Energy counters erasing
0
No change
1
Resetting the received active energy
counter
2
Resetting the provided active energy
counter
3
Resetting the reactive inductive
energy counter
4
Reset of reactive capacity energy
counter