Chapter 7 Exclusive Functions for iS7 Inverter Control/Monitoring
7-18
▶
Application and exemplary program
1) Set up inverter parameters as follows. Especially, enter 0305Hex which is the address of the inverter
operation status (app. 4-1, page 4, Appendix) in the APO76 (PLC Rd Data1).
Code
Function Name
Set Value
Remark
DRV01
Cmd Frequency
12.00 Hz
-
DRV06 Cmd
Source Keypad
-
DRV07 Freq
Ref
Src Keypad-1 -
APO76
PLC Rd Data1
0305 Hex
-
2) The APO76 (PLC Rd Data1) corresponds by 1:1 with the PLC option’s special register D4474.
Therefore, the value in the D4474 is the data (current operation status of the inverter) stored in 0305Hex
which is the address of the inverter operation status registered in the APO76 (PLC Rd Data1).
3) For an example with the ladder program below, PLC option can monitor the current operation status
(stop, accelerating, decelerating, constant speed, etc.) of the inverter.
4) In stopped status, the D4474 is “h0000” (see common area of inverter)
5) Now, press the FWD key on the digital loader of the inverter to provide it with forward operation
reference. During forward operation, the D4474 is h0021 (see common area of inverter)