SFA-5000 • SFA-10000 CANopen®
6.8.3 Standardised Device Profile Area objects (DS 406)
6000-00 Operating parameters
[Unsigned16, rw]
Bit
Function
bit = 0
bit = 1
0
Count up
information
rewinding the
wire
Count up
information
pulling the
wire out
1
not used
2
disabled
enabled
3 … 11
not used
12
disabled
enabled
13
disabled
enabled
14 and 15
not used
Default values are highlighted in bold
Default = 0001h
Code sequence
This is intended to set whether the count increases (count up information) when
you rewind the wire or when you pull the wire out.
Setting 0 (bit 0
= 0) causes the position value to increase when
you rewind the wire; on the contrary, setting 1 (bit 0
causes the position value to increase when you pull the wire out.
Default = 1
is currently set to to “Count up
information rewinding the wire” or “Count up information pulling the wire out”,
you can read the bit 0
object, see on page 70.
Scaling function
When this option is disabled, the device uses the p hysical resolution values (see
the
6501-00 Physical singleturn resolution
hardware distinguishable revolutions
objects); if it is enabled, it uses the
6001-00 Measuring units per revolution
objects with the following relation:
Transmitted position =
6001-00 Measuring units per revolution
real position
6501-00 Physical singleturn resolution
6001-00 Measuring units per revolution
equal to or less than the value in the
6501-00 Physical singleturn resolution
MAN SFA_5000_10000_CB E 1.0.odt
6 - CANopen® interface
59 of 88