MODBUS Register Map v1.48, Rx104P
248083336-1 Rev 3
A-15
These registers run in parallel with the data registers (30xxx series).
For example, data register 30010’s enable register would be 43010.
Data register 30016’s enable register would be 43016.
Note:
Alarm Enable
currently only works for
Particle Channels.
The user can enable multiple particle channels for alarming at the same
time.
Particle data registers for the Enable setting start at 43009 for the high
word and 43010 for the low word for particle channel 1.
Table A-14 Alarm Enable Registers
Register
Data Type
Description
43009
unsigned int
Enable for Particle Channel 1 [high] (smallest
particle size starts here)
43010
unsigned int
Enable for Particle Channel 1 [low]
43011
unsigned int
Enable for Particle Channel 2 [high]
43012
unsigned int
Enable for Particle Channel 2 [low]
43013
unsigned int
Enable for Particle Channel 3 [high]
43014
unsigned int
Enable for Particle Channel 3 [low]
43015
unsigned int
Enable for Particle Channel 4 [high]
43016
unsigned int
Enable for Particle Channel 4 [low]
43017
unsigned int
Enable for Particle Channel 5 [high]
43018
unsigned int
Enable for Particle Channel 5 [low]
43019
unsigned int
Enable for Particle Channel 6 [high]
43020
unsigned int
Enable for Particle Channel 6 [low]
43021
unsigned int
Enable for Particle Channel 7 [high]
43022
unsigned int
Enable for Particle Channel 7 [low]
43023
unsigned int
Enable for Particle Channel 8 [high]
43024
unsigned int
Enable for Particle Channel 8 [low]
43041
unsigned int
Enable for Analog Channel 1 [high]
43042
unsigned int
Enable for Analog Channel 1 [low]
43043
unsigned int
Enable for Analog Channel 2 [high]
43044
unsigned int
Enable for Analog Channel 2 [low]
Summary of Contents for REMOTE 3104P
Page 1: ......
Page 2: ...00...
Page 3: ...Lighthouse Worldwide Solutions REMOTE 3104P 5104P Airborne Particle Counter Operating Manual...
Page 6: ......
Page 10: ...Lighthouse REMOTE 3014P 5104P Operating Manual t iv 248083336 1 Rev 3...
Page 12: ...Lighthouse REMOTE 3014P 5104P Operating Manual ii 248083336 1 Rev 3...
Page 40: ...Lighthouse REMOTE 3104P 5104P Operating Manual 4 10 248083336 1 Rev 3...
Page 54: ...Lighthouse REMOTE 3104P 5104P Operating Manual 6 12 248083336 1 Rev 3...
Page 74: ...Lighthouse REMOTE 3104P 5104P Operating Manual B 2 248083336 1 Rev 3...
Page 76: ...Lighthouse REMOTE 3104P 5104P Operating Manual C 2 248083336 1 Rev 3...
Page 81: ...00...
Page 82: ......