7. MAINTENANCE
97
ENGLISH
Inspection category
Cooling water
Condensing
pressure (temp.)
Heat exchanging status
Chilled water
Vaporizing pressure
(temp.)
Heat exchanging status
Refrigerant filling
amount
B
oiling status
Refrigerant
contamination
Oil amount
Oil filling amount
Oil leakage
Chilled water
flow switch
Cooling water
flow switch
Decrease cooling water amount to
check the operation
Decrease chilled water amount to
check the operation
Lubrication system visual inspection
Accumulated filling amount after
filling new refrigerant
Visual inspection
Visual inspection
Check through site glass
Difference between cold water outlet
temp. and vaporizing temp.
Check with manometer
(thermometer)
Check with thermometer
Check with thermometer
Difference between condensing
temp. and coolant outlet temp.
Check with manometer
(thermometer)
Check with thermometer
Check with thermometer
3
4°C or less
(standard condition)
24°C or more
(standard condition)
6~10 kg/cm
2
(26~42 °C)
2~5 kg/cm
2
(0~21 °C)
kg/cm
2
(°C)
kg/cm
2
(°C)
°C
°C
°C
°C
1~
3
°C
1~
3
°C
6~15 °C
4°C or more
Refer to 10.5 standard
filling amount
Whether contaminating
material, moisture,
oil is included
Check with site glass
on the gear box during
operation
Refer to 10.5 standard
filling amount
Month
Day
Check through site glass
Inlet
Outlet
Inlet
Outlet
C
ondenser
E
v
aporat
or
L
ubrication sy
st
em
Saf
et
y Device
Inspection method
Standard
Decision
(OX)
Actual
measurement
Table 14 Periodical maintenance and inspection table