7. MAINTENANCE
ENGLISH
- Lubrication system daily inspection standard
- Evaporator daily inspection standard
* If the evaporation pressure becomes low, the copper tubes in the evaporator will freeze causing danger to break-
down. The major reasons for the lowering of the evaporation pressure are insufficient refrigerant, lowering water
temperature and poor heat exchanging.
* As in the case of condenser tube, if foreign material is entered into tube or scale is attached to tube, corrosion may
occur, lowering the heat exchanging capacity.
Figure 59 Evaporator daily inspection standard
Classification
Inspection items
Inspection method
Standard
Evaporator
Chilled water
Inlet
Check in the panel
5~15°C or lower
Outlet
Check in the panel
3°C or higher
Evaporation pressure(temper-
ature)
Check in the panel
2 ~ 5 kg/cm²(R134a)
4 ~ 8 kg/cm²(R22)
Heat exchanging status
Difference between evaporation
temperature and chilled water
outlet temperature
0.5~3°C
Amount of refrigerant charged Check through sight-glass
Refrigerant status
Check through sight-glass
Classification
Inspection items
Inspection method
Standard
Oil
Oil amount
Visual check
Oil surface exists on the sight-
glass
Leakage
Oil system visual check
There should be no leakage.
Figure 60 Lubrication system daily inspection standard