How to act for the problem (2/4)
105
8. TROUBLESHOOTING
ENGLISH
Problem item
Displayed contents
Cause
Action
Condenser 2 pressure sen-
sor
Condenser pressure
sensor 2 problem
Sensor disconnected/short-
circuit
Main board malfunction
Check part condition or wiring
Replace part or re-wire
Condenser pressure sensor
Evaporator pressure
sensor problem
Sensor disconnected/short-
circuit
Main board malfunction
Check part condition or wiring
Replace part or re-wire
Evaporator pressure sensor
Condenser pressure
sensor problem
Sensor disconnected/short-
circuit
Main board malfunction
Check part condition or wiring
Replace part or re-wire
Current sensor 2
Current sensor 2
problem
Sensor disconnected/short-
circuit
Main board malfunction
Check part condition or wiring
Replace part or re-wire
Current sensor 1
Current sensor 1
problem
Sensor disconnected/short-
circuit
Main board malfunction
Check part condition or wiring
Replace part or re-wire
Compressor discharge tem-
perature
Compressor dis-
charge temperature
Compressor discharge tem-
perature high
Check compressor discharge tem-
perature displayed on the micom
screen.
Check the set value and correct if
it is wrong.
Compressor discharge tem-
perature 2
Compressor dis-
charge temperature 2
Compressor discharge tem-
perature high
Check compressor discharge tem-
perature displayed in the micom
screen.
Check the set value and correct if
it is wrong.
Compressor 1 current
Compressor 1 current
abnormal
Compressor current is de-
tected to be higher than set
value.
Check compressor current dis-
played in the micom screen.
Check the set value and correct if
it is wrong.
Compressor 2 current
Compressor 2 current
abnormal
Compressor current is de-
tected to be higher than set
value.
Check compressor current dis-
played in the micom screen.
Check the set value and correct if
it is wrong.
Condenser 2 pressure
Condenser pressure
high abnormal
Condenser pressure is de-
tected to be either higher
than or lower than set value.
Check condenser pressure dis-
played in the micom screen.
Check the set value and correct if
it is wrong.
Refrigerant differential pres-
sure 2
Refrigerant differen-
tial pressure 2 low
abnormal
Differential pressure be-
tween evaporator and con-
denser is lower than set
value.
Check condenser pressure
Check evaporator pressure
Check status of pressure sensitive
switch contact or wiring.
Replace part or re-wire