4. CONTROL SYSTEM
ENGLISH
Protection logic
4-7. Product Protection Function
Check points before inspection
Classification
Contents
Cause
Operation
Status
Sensor(s)
Temperature, Pressure,
Current sensor problem
Temperature, Pressure, Cur-
rent sensor abnormal de-
tected
Chiller stop
Problem
Interlock
Chilled water pump interlock
abnormal
Pump interlock abnormal
during Operation -detected
Chiller stop
Problem
Cooling water pump inter-
lock abnormal
Pump interlock abnormal
during Operation -detected
Chiller stop
Problem
Chilled water flow rate low
abnormal
Flow rate interlock abnormal
during Operation detected
Chiller stop
Problem
Cooling water flow low rate
abnormal
Flow rate interlock abnormal
during Operation detected
Chiller stop
Problem
Temperature &
Pressure
Condenser high pressure
abnormal
Condenser pressure high -
detected
Chiller stop
Problem
Evaporator low pressure ab-
normal
Evaporator pressure low –
detected
Chiller stop
Problem
Evaporator refrigerant tem-
perature low abnormal
Evaporator refrigerant tem-
perature low abnormal de-
tected
Chiller stop
Problem
Compressor discharge high
temperature abnormal
Compressor discharge high
temperature abnormal de-
tected
Chiller stop
Problem
Compressor discharge high
temperature abnormal
Compressor discharge high
temperature abnormal de-
tected
Chiller stop
Problem
Chilled water low tempera-
ture abnormal
Chilled water outlet temper-
ature low abnormal de-
tected
Chiller stop
Problem