4. CONTROL SYSTEM
ENGLISH
!
CAUTION
When changing the setting values, check the specifications with the manufacturer before making the change.
Since the system can be damaged due to the changes in the setting value, make sure to consult manufacturer
before setting values.
1. Control calculation cycle
Output value is calculated on every setting time based on the deviation value between cold water outlet tempera-
ture and inlet.
2. Cold water control temperature dead band
If the cold water outlet temperature is within the value of cold water outlet temperature ± "Cold water control tem-
perature dead band", the controller does not control the cold water outlet temperature and stop the operation.
3. Motor rated current
Set the rated current of the screw compressor motor.
4. Motor rated voltage
This menu is for setting the rated voltage of compressor motor. There is no control function and it is used for dis-
play purpose only. A separate voltage sensor should be installed.
5. Model selection
This menu is for setting the machine type.
This controller is set the control method to be changed automatically, based on the setting of the machine type.
For setting the machine type, please make changes after consulting the LG experts.
An arbitrary change can damage the machine.
6. Smooth startup output cycle
7. Smooth startup output time
This menu is used when control valve selection is set on “Stepless”.
Smooth startup output cycle refers to the interval of the valve movements, and the smooth startup output time is
(set to-??) the maximum time of ON (Close) output of the valve within the smooth startup output cycle.
8. Control valve selection
This menu is used for selecting the output method of the capacity control valve of the compressor.
The capacity control method is decided when installing the compressor. Therefore before setting, check the model
of the compressor.
9. Motor rated current 2
Select the rated current of Compressor 2.
Set the rated current after checking the rated value and specifications of the compressor motor.
Since it is the reference value of motor current control and current abnormality control, be careful when setting.
10. Communication mode selection
This controller can be set in 2 communication methods to communicate externally.
Check the connected system before setting.
11. Economizer valve opening temperature
This menu is used when economizer is installed in the screw chiller.
Reference temperature of the setting value is the compressor discharge temperature value. Check whether the
economizer is installed.
12. Liquid valve opening temperature
13. Liquid valve closing temperature
Liquid valve is operated to protect the compressor when the compressor discharge temperature suddenly rises.
Reference temperature value is the compressor discharge temperature. A separate valve should be installed for
use.