Service Manual 117
4) Troubleshooting CH05, CH53
04
/
53
Communication
(Indoor
→
Outdoor)
• Communication poorly
• Power input AC 220V. (Outdoor, Indoor)
• The connector for transmission is disconnected.
• The connecting wires are misconnected.
• The GND1,2 is not connected at main GND.
• The communication line is shorted at GND.
• Transmission circuit of outdoor PCB is abnormal.
• Transmission circuit of indoor PCB is abnormal.
Display
code
Title
Cause of error
Check point & Normal condition
Check Point
1. Check the input power AC380~450V. (Outdoor, Indoor unit)
2. Check the communication wires are correctly connected.
→
Adjust the connection of wire
→
Confirm the wire of “Live”, “Neutral”
3. Check the resistance between communication line and GND.
(Normal : Over 2M
Ω
)
4. Check the connector for communication is correctly
connected.
5. Check the connection of GND1, GND2, and main GND.
6. If one indoor unit is operated normally, outdoor PCB is no
problem.
→
Check the another indoor unit.
* CH05 is displayed at indoor unit, CH53 is displayed at outdoor
unit.
Troubleshooting Guide
Summary of Contents for L8UC100BFA0
Page 92: ...92 Multi type Air Conditioner Schematic Diagram 2 Outdoor Unit 1 L8UC100BFA0 L8UH100BFA0 ...
Page 95: ...Service Manual 95 L8UH100BFA0 L8UC100BFA0 Schematic Diagram 2 Outdoor Unit ...
Page 97: ...Service Manual 97 2 Duct Type High static BH BG BE chassis Schematic Diagram ...
Page 98: ...98 Multi type Air Conditioner Schematic Diagram Low static BT BT1 chassis ...
Page 99: ...Service Manual 99 4 way TE TF TD chasis 58 B Schematic Diagram ...
Page 100: ...100 Multi type Air Conditioner Schematic Diagram 2 Display ASSEMBLY 1 Split Type ...
Page 153: ...P No 3828A22009L October 2005 Printed in Korea ...