Service Manual 53
Installation
■
Installation of main unit
:
• This unit has two different installation types:
(1) Ceiling-suspended type and (2) wall-mounted type.
• Choose the proper installation pattern according to the
location of installation.
• The installation location for printed wiring board can be
changed.
Follow the procedure specified in the "CONNECTING
THE WIRING" section to change the location.
NOTICE
(1) Ceiling-suspended type
(2) Wall-mounted type
Scre
Screws(M5)
ws(M5)
(locally procude)
(locally procude)
Screws(M5)
(locally procude)
BD unit
Six-sided Nut
(M10 or M8)
Six-sided Nut
(M10 or M8)
Hanger metal
Hanger metal
Flat washer
Flat washer
Hanging bolt
Hanging bolt
(M10 or M8)
15.00
Procedure
(1) Fix the fumished hanger metal with two screws.(4 locations in
total).
(2) Using an insert-hole-in- anchor, hang the hanging bolt.
(3) Install a hexagon nut and a flat washer (locally-procured)to
the hanging bolt as shown in the figure in the left, and ift the
main unit to hang on the hanger metal.
(4) After checking with a level that the unit is level, tighten the
hexagon nut.
* The tilt of the unit should be within ±5° in front/back and
left/right.
Procedure
(1) Fix the fumished hanger metal with two screws.
(3 locations in total).
(2) After checking with a level that the unit is level, fix the unit
with the furnished wood screws.
* The tilt of the unit should be within ±5° in front/back and
left/right.
* Block up the parts of hanger holes (2 places) by using insu-
lation PE after installing the hanger.
CAUTION
• Once a screw-hole on the main unit has had a screw hammered in, make sure to either hammer it again or cover it
with alumium tape.(This is to prevent condensation)
• Be sure to install the unit with the ceiling-sie up.
• Do not install near bedrooms. the sound of refrigerant flowing through the piping may sometimes be audible.
(1) Ceiling-suspended type
(2) Wall-mountde type
Summary of Contents for L8UC100BFA0
Page 92: ...92 Multi type Air Conditioner Schematic Diagram 2 Outdoor Unit 1 L8UC100BFA0 L8UH100BFA0 ...
Page 95: ...Service Manual 95 L8UH100BFA0 L8UC100BFA0 Schematic Diagram 2 Outdoor Unit ...
Page 97: ...Service Manual 97 2 Duct Type High static BH BG BE chassis Schematic Diagram ...
Page 98: ...98 Multi type Air Conditioner Schematic Diagram Low static BT BT1 chassis ...
Page 99: ...Service Manual 99 4 way TE TF TD chasis 58 B Schematic Diagram ...
Page 100: ...100 Multi type Air Conditioner Schematic Diagram 2 Display ASSEMBLY 1 Split Type ...
Page 153: ...P No 3828A22009L October 2005 Printed in Korea ...