54 Multi type Air Conditioner
Installation
■
Connection of Piping
• When connecting indoor units, make sure to connect refrigerant pipes and connection wires to the appropriate connection ports
maked with matching alphabets. (A, B, C, D)
:
• Be sure to mark all the local refrigerant piping(liquid pipes, gas pipes,
etc.) for each indoor unit designating clearly which room it belongs
in.(A, B, C, D)
NOTICE
:
For flaring work the piping, follow the instructions in the installation manual to each unit.
NOTICE
Connecting the pipings to the in door unit
and drain hose to drain pipe
1. Align the center of the pipings and sufficiently tight-
en the flare nut by hand.
2. Tighten the flare nut with a wrench.
Wrap the insulation material around the
connecting portion.
1. Overlap the connection pipe insulation material and
the indoor unit pipe insulation material. Bind them
together with vinyl tape so that there is no gap.
2. Wrap the area which accommodates the rear piping
housing section with vinyl tape.
Close up a socket out of use with a brass
cap.
1. Align the center of the piping and sufficiently tighten
the brass cap by hand.
2. Tighten the brass cap with a wrench.
3. Wrap the area contacted with insulation.
BD Unit Socket
Flare nut
Pipes
Wrench
BD Unit Socket
Open-end wrench (fixed)
Connection pipe
Flare nut
mm
inch
kg.m
Ø6.35
1/4
1.8
Ø9.52
3/8
4.2
Ø12.7
1/2
5.5
Ø15.88
5/8
6.6
Ø19.05
3/4
6.6
Outside diameter
Torque
Vinyl tape(narrow)
BD Unit
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
BD Unit Socket
Pipe sealed
or welded
Brass cap
A
B
C
D
CAUTIONS
• Never use the plastic cap for sealing.
• Make sure to use brass cap with the end of
pipe sealed or welded tightly.
Summary of Contents for L8UC100BFA0
Page 92: ...92 Multi type Air Conditioner Schematic Diagram 2 Outdoor Unit 1 L8UC100BFA0 L8UH100BFA0 ...
Page 95: ...Service Manual 95 L8UH100BFA0 L8UC100BFA0 Schematic Diagram 2 Outdoor Unit ...
Page 97: ...Service Manual 97 2 Duct Type High static BH BG BE chassis Schematic Diagram ...
Page 98: ...98 Multi type Air Conditioner Schematic Diagram Low static BT BT1 chassis ...
Page 99: ...Service Manual 99 4 way TE TF TD chasis 58 B Schematic Diagram ...
Page 100: ...100 Multi type Air Conditioner Schematic Diagram 2 Display ASSEMBLY 1 Split Type ...