Service Manual 45
Installation
Ceiling
1~3mm
Drainage hole
Drainage hole
U-Trap
B
C
A
≥
70mm
B
≥
2C
C
≥
2 x SP
SP = External Pressure
(mmAq)
Ex) External Pressure
= 10mmAq
A
≥
70mm
B
≥
40mm
C
≥
20mm
A
Make sure to be closed.
Unit
Drainage pipe
(Local supply)
Thermal insulator
(Local supply)
Drainage hole
CAUTION FOR GRADIENT OF
UNIT AND DRAIN PIPING
Lay the drain hose with a downware
inclination so water will drain out.
700mm
(Drain pump model only)
Front of view
• Always lay the drain with downward inclination
(1/50 to 1/100).
Prevent any upward flow or reverse flow in any part.
• 5mm or thicker formed thermal insulator shall
always be provided for the drain pipe.
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 5mm.
• The unit must be horizontal or declined to the drain hose connected when finished installation.
CORRECT
INCORRECT
• Upward routing not
allowed
Applied U-Trap Dimension
• Install the P-Trap (or U-Trap) to prevent
a water leakage caused by the blocking
of intake air filter.
INCORRECT
CORRECT
2. Duct Type Indoor Unit
Summary of Contents for L8UC100BFA0
Page 92: ...92 Multi type Air Conditioner Schematic Diagram 2 Outdoor Unit 1 L8UC100BFA0 L8UH100BFA0 ...
Page 95: ...Service Manual 95 L8UH100BFA0 L8UC100BFA0 Schematic Diagram 2 Outdoor Unit ...
Page 97: ...Service Manual 97 2 Duct Type High static BH BG BE chassis Schematic Diagram ...
Page 98: ...98 Multi type Air Conditioner Schematic Diagram Low static BT BT1 chassis ...
Page 99: ...Service Manual 99 4 way TE TF TD chasis 58 B Schematic Diagram ...
Page 100: ...100 Multi type Air Conditioner Schematic Diagram 2 Display ASSEMBLY 1 Split Type ...
Page 153: ...P No 3828A22009L October 2005 Printed in Korea ...