56 Multi type Air Conditioner
Operation
1. MAIN UNIT FUNCTION
• DISPLAY
Operation Indicator
• On while in appliance operation, off while in appliance pause
• Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)
Sleep Timer Indicator
• On while in sleep timer mode, off when sleep timer cancel or appliance operation pause
Timer Indicator
• On while in timer mode (on/off), off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control
■
Cooling Mode Operation
• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan
stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp
➲
Setting Temp+0.5°C
Compressor OFF Temp
➲
Setting Temp-0.5°C
• While in compressor running, operating with the airflow speed set by the remote control. While compressor is
off fan operates at low speed regardless of the setting.
■
Soft Dry Operation Mode
• When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C
≤
Intake Air Temp
➲
25°C
24°C
≤
Intake Intake Air Temp<26°C
➲
Intake Air Temp-1°C
18°C
≤
Intake Intake Air Temp<24°C
➲
Intake Air Temp-0.5°C
Intake Air Temp<18°C
➲
18°C
• While compressor off, the indoor fan repeats low airflow speed and stop.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat.
Compressor ON Temp.
➲
Setting Temp+0.5°C
Compressor OFF Temp.
➲
Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
■
Heating Mode Operation
• When the intake air temp r3°…above the setting temp, the compressor is turned off. When below the
setting temp, the compressor is turned on.
Compressor ON Temp.
➲
Setting Temp.
Compressor OFF Temp.
➲
Setting Temp.+3°C
• While compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 27°C , it
Function of control
Operation
Summary of Contents for L8UC100BFA0
Page 92: ...92 Multi type Air Conditioner Schematic Diagram 2 Outdoor Unit 1 L8UC100BFA0 L8UH100BFA0 ...
Page 95: ...Service Manual 95 L8UH100BFA0 L8UC100BFA0 Schematic Diagram 2 Outdoor Unit ...
Page 97: ...Service Manual 97 2 Duct Type High static BH BG BE chassis Schematic Diagram ...
Page 98: ...98 Multi type Air Conditioner Schematic Diagram Low static BT BT1 chassis ...
Page 99: ...Service Manual 99 4 way TE TF TD chasis 58 B Schematic Diagram ...
Page 100: ...100 Multi type Air Conditioner Schematic Diagram 2 Display ASSEMBLY 1 Split Type ...
Page 153: ...P No 3828A22009L October 2005 Printed in Korea ...