30
Remove the terminal block access cover
on the upper back of the dryer. Install a
UL-listed strain relief into the power cord
through-hole; then thread a UL-listed, 30A,
240V, 4-wire, #10 AWG-minimum copper
conductor power cord through the
strain relief.
Transfer the dryer’s ground wire from behind
the green ground screw to the center screw
of the terminal block. Attach the two hot
leads of the power cord to the outer terminal
block screws. Attach the white neutral wire
to the center terminal block screw. Attach the
power cord ground wire to the green ground
screw. TIGHTEN ALL SCREWS SECURELY.
Reinstall the terminal block access cover.
UL-Listed
Strain Relief
UL-Listed
4-Wire
Power Cord
Terminal
Block
Ground Screw
Neutral
(White)
Hot
(Black)
Power Cord
Ground Wire
Hot
(Red)
• A 4-wire connection is required for all mobile
and manufactured home installations, as well
as all new construction after January 1, 1996.
• A UL-listed strain relief is required.
• Use a 30-amp, 240V, UL-listed power cord
with #10 AWG-minimum copper conductor
and closed loop or forked terminals with
upturned ends.
WARNING:
Connect the power co r d to the terminal block. Each colo r ed wi r e should be connected to
same color sc r e w . Wi r e color indicated on manual is connected to the same color sc r ew
in block. Failu r e to follow these instructions may r esult in a short or overload.
G r ounding th r ough the neutral conductor is p r ohibited for: (1) new branch-ci r cuit
installations, (2) mobile homes, (3) r ec r eational vehicles, and (4) a r eas whe r e local
codes p r ohibit g r ounding th r ough the neutral conducto r .
!
Summary of Contents for GDL1329CED3
Page 13: ...13 4 INITIAL STEPS FOR INSTALLING YOUR DRYER ...
Page 14: ...14 ...
Page 15: ...15 ...
Page 16: ...16 ...
Page 17: ...17 ...
Page 28: ...28 ...
Page 29: ...29 6 ELECTRICAL REQUIREMENTS FOR ELECTRIC DRYERS ...
Page 36: ...36 9 EXHAUST REQUIREMENTS AND MAINTENANCE ...
Page 40: ...40 10 DRYER CYCLE PROCESS ...
Page 42: ...42 44 ...
Page 43: ...43 ...
Page 44: ...44 12 MOTOR DIAGRAM AND SCHEMATIC Centrifugal switch Centrifugal switch Pull Drive forward ...
Page 45: ...45 13 CONTROL LAY OUT PWB ASSEMBLY DISPLAY LAY OUT PWB ASSEMBLY LAY OUT ...
Page 50: ...50 ...
Page 51: ...51 Trouble Symptom Measurement Condition Air TEMP RES k Air TEMP RES k Air TEMP RES k ...
Page 55: ...55 Trouble Symptom Measurement Condition ...
Page 56: ...56 Trouble Symptom Measurement Condition ...
Page 57: ...57 16 ERROR MODE ...
Page 61: ...61 18 CHANGE GAS SETTING NATURAL GAS PROPANE GAS ...
Page 62: ...62 ...
Page 71: ...71 EXPLODED VIEW 20 20 1 1 Control Panel Plate Assembly Coin OPL Type A210 A120 A116 A110 ...
Page 72: ...72 20 1 2 Control Panel Plate Assembly Card Type A210 A120 A117 A116 A110 ...