2. Specifications
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB
Piping Length: - Interconnecting Piping Length 5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without notic for purpose of improvement.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
Model Name
B42AWYN745A
B55AWYN7G5A
Power Supply
V, Ø, Hz
Power Input
kW
Running Current
A
Dimensions
Body
W x H x D
mm
W x H x D
inch
Net Weight
Body
kg (lbs)
Heat
Exchanger
(Row x Column x Fins per inch) x No.
-
Face Area
m
2
(ft
2
)
Fan
Type
-
Air
Flow
Rate
High-static
Mode
(Factory
Set)
H / M / L
m
3
/min
H / M / L
l/s
External Static
Pressure
Pa (mmAq)
External Static Pressure
Min.~Max. Pa (mmAq)
Fan Motor
Type
-
Output
W x No.
Dehumidification Rate
l
/ h (pts/h)
Sound Pressure Level
H / M / L
dB(A)
Piping
Connections
Liquid
mm(inch)
Gas
mm(inch)
Drain (O.D. / I.D.)
mm
Safety Devices
-
-
Power and Communication Cable (included Earth)
No. x mm
2
(AWG)
220-240, 1, 50
220-240, 1, 50
0.48
0.48
2.1
2.1
1,320 × 400 × 534
1,320 × 400 × 534
51-31/32 × 15-3/4 × 21-1/32
51-31/32 × 15-3/4 × 21-1/32
48.0 (105.8)
48.0 (105.8)
(3 × 16 × 21) × 1
(3 × 16 × 21) × 1
1.2 (2.6)
2.0 (4.3)
Sirocco Fan
Sirocco Fan
48.0 / 42.0 / 36.0
60.0 / 50.0 / 40.0
800 / 700 / 600
1,000 / 833 / 667
70 (7.1)
80 (8.1)
60~200 (6.1~20.4)
60~200 (6.1~20.4)
BLDC BLDC
400 x 1
195 x 2
0.67 (1.4)
2.2 (4.6)
45 / 44 / 43
46 / 45 / 44
Ø 9.52 (3/8)
Ø 9.52 (3/8)
Ø 15.88 (5/8)
Ø 15.88 (5/8)
Ø 32 / 25
Ø 32 / 25
Fuse Fuse
- -
4C x 1.0 (18)
4C x 1.0 (18)